| 2003-10-03 00:00:00 | 1) ALL NEW LODGING OR ROOMING HOUSES |
| | SHALL BE PROTECTED WITH AN AUTOMATIC |
| | FIRE SPRINKLER SYSTEM. |
| | |
| | 2) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWINGS. A MINIMUM OF 6" |
| | NUMERALS REQUIRED. |
| | |
| | 3) RISE AND TREAD SIZES ARE WRONG FOR |
| | THE STAIRS. TREADS SHALL BE A MINIMUM |
| | OF 11" WIDE. RISERS SHALL BE A MINIMUM |
| | OF 4" AND A MAXIMUM OF 7". |
| | |
| | 4) WINDOW AND AT LEAST ONE DOOR NOTED |
| | WITHIN 10 FEET OF EXIT STAIR. |
| | |
| | 5) SMOKE DETECTORS ON FIRST FLOOR |
| | MAY BE LOCATED TOO CLOSE TO BATHROOMS |
| | WHERE STEAM WOULD CAUSE FALSE ALARMS. |
| | |
| | 6) PLEASE EXPLAIN EXITING RATIONALE |
| | FROM SECOND FLOOR. IT APPEARS A SINGLE |
| | EXIT IS PROVIDED. IS NO SECONDARY EXIT |
| | OR MEANS OF ESCAPE PROVIDED. |
| | |
| | 7) NO HANDRAILS PROVIDED AT THE TWO |
| | SETS OF STEPS FROM THE FRONT PORCH. |
| | |
| | 8) NO FIRE ALARM SYSTEM INDICATED ON |
| | DRAWINGS. |
| | |
| | 9) NO INTERIOR FINISH INFORMATION |
| | PROVIDED FOR WALLS AND CEILINGS. |
| | |
| | 10) PLEASE INDICATE ANY TENANT OR |
| | FLOOR SEPARATIONS BETWEEN SUITES. |
| | |
| | 11) BATHROOM AND CLOSET DOORS SHALL |
| | MEET CERTAIN REQUIREMENTS. CLOSET |
| | DOORS SHALL BE OPERABLE FROM THE |
| | INSIDE. BATHROOM DOORS SHALL BE |
| | OPENABLE FROM THE OUTSIDE. |
| | |
| | 12) BUILDING MAY BE LOCATED IN THE |
| | CITY FIRE LIMITS. CERTAIN RESTRICTIONS |
| | MAY APPLY. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |