| Date |
Text |
| 2003-10-24 00:00:00 | THIS BUILDING WILL BE AN R1 OCCUPANCY |
| | AND IS REQUIRED TO BE DESIGNED, SIGNED, |
| | SEALED AND DATED BY A FLORIDA |
| | REGISTERED ARCHCITECT OR ENGINEER.THE |
| | ENGINEER SENG-CHAI TAN DECLARES |
| | STRUCTURAL RESPONSIBILITY ONLY.THE |
| | REMAINDER OF THE DESIGNMUST BE BY AN |
| | ARCHITECT OR ENGINEER ALSO. |
| | |
| | THIS BUILDING WILL BE LOCATED IN THE |
| | DESIGNATED FIRE DISTRICT AND MUST |
| | COMPLY WITH FBC F102.2.5, AS AMENDED BY |
| | THE CITY,WHICH REQUIRES TWO STORY |
| | BUILDINGS TO BE ONE HOUR PROTECTED |
| | UNLESS, FIRE SPRINKLERED THROUGH OUT |
| | OR OF TYPE III CONSTRUCTION.PLEASE |
| | REVISE AS NECESSARY. |
| | |
| | THE WINDOW BUCKS ON SHEET A1 MUST COMPLY |
| | WITH FBC 1707.4.4. |
| | |
| | FBC TABLE 600 REQUIRES A TWO HOUR FIRE |
| | RATED EXTERIOR WALL WHEN LOCATED FROM |
| | THREE TO TEN FEET OF A COMMON OR |
| | ASSUMED PROPERTY LINE, AND FBC |
| | 705.1.1.2 REQUIRES PROTECTED OPENINGS. |
| | THE EAST AND WEST ELEVATIONS ARE |
| | SUBJECT TO THIS. |
| | |
| | SHOW HOW THE EXISTING BUILDING TO THE |
| | EAST WILL COMPLY WITH TABLE 600 AND THE |
| | ASSUMED PROPERTY LINE.SEE FBC 504. |
| | SEE ALSO FBC 1006.2.2 FOR THE EXTERIOR |
| | STAIR EXPOSURE ALLOWANCE. |
| | |
| | PLEASE PROVIDE A SITE PLAN WITH |
| | TOPOGRAPHIC INFORMATION SO THAT |
| | HANDICAP SITE ACCESSIBILITLY MAY BE |
| | DETERMINED. |
| | |
| | THE WINDOWS, DOORS AND ANY OTHER |
| | OPENINGS IN THE TEN FEET PRESCRIBED |
| | AREA FOR THE STAIRS AS NOTED INFBC |
| | 1006.2.4 MUST BE PROTECTED. |
| | |
| | SHEET A2.PLEASE CLARIFY THE |
| | REINFORCEMENT SCHEDULE FOR THE F2 PADS |
| | WITH 4 #5'S VERTICAL. |
| | |
| | HOW WILL THE WOOD COLUMNS CONNECT TO |
| | THE PADS?ABOVE OR BELOW GRADE? |
| | |
| | ENGINEER, PLEASE CLARIFY THE COLUMN |
| | SCHEDULE AS TO 8X12 BLOCK 8X8 BLOCK, |
| | ETC.ARE THESE IN FACT COLUMNS OR |
| | REINFORCED MASONRY?SEE ACI 530-99 AND |
| | PROVIDE THE REQUISITE SPECIFICATIONS |
| | AND DETAILS.SHOW THE DELEGATED |
| | ENGINEERING REQUIREMENTS FOR THE ROOF |
| | AND FLOOR TRUSSES. |
| | |
| | SHEET A5, SEE FBC 1608.2 FOR THE |
| | MINIMUM STRUCTURAL DESIGN CRITERIA FOR |
| | HAND AND GUARD RAILS. |
| | |
| | THE STAIR RISE AND RUN DOESN'T COMPLY |
| | WITH FBC 1007.3.ALSO, SHOW A |
| | CONSTRUCTIONDETAIL, INCLUDING |
| | FASTENERS, FOUNDATION AND DESIGN LOADS |
| | FOR THE STAIRS, |
| | BALCONIES, ETC. |
| | |
| | SHOW THE ATTIC ACCESS AND VENTILATION AS |
| | PROVIDED FOR IN FBC 2309.6 AND 2309.7. |
| | |
| | SHOW THE STAIR AND HAND RAIL DETAILS FOR |
| | THE FRONT PORCH, (SOUTH ELEVATION). |
| | |
| | HOW WILL THE HANDICAP TOILETS ON THE |
| | NORTH SIDE BE ACCESSED?THE PORCH IS |
| | SHOWN 20" ABOVE THE SURROUNDING GRADE. |
| | |
| | PLEASE PROVIDE THE FIRE DESIGN NUMBER |
| | FOR THE RATED WALLS, FLOORS, ROOF AND |
| | COLUMN ASSEMBLIES TOGETHER WITH THE |
| | METHOD OF PENETRATION PROTECTION.SEE |
| | FBC 104.2 AND FBC 701. |
| | |
| | SHEET A5 SEC AA, WHAT IS THE SPACING |
| | FOR THE 3/4" BOLT THROUGH THE 2-2X8'S? |
| | |
| | THE ENERGY CODE DECLARES R30 CEILING |
| | INSULATION NOT SHOWN ON THE PLANS. |
| | PLEASE REVISE AS NECESSARY. |
| | |
| | SEE FBC 13-600.3 FOR THE REQUIREMENT OF |
| | AN ARCHITECT OR ENGINEER TO SIGN AND |
| | SEAL THE ENERGY CODE AND INCORPORATE |
| | THEM INTO THE PLANS AND SPECIFICATIONS. |
| | |
| | SHOW THE DRAFTSTOPPING IN ACCORDANCE |
| | WITH FBC 2305.2.2. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO THE |
| | COUNTY, THE PERMIT PLANS STAMPED BY |
| | THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |