Plan Review Notes
Plan Review Notes For Permit 03081533
Permit Number 03081533
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-09-16 00:00:001) SITE PLAN HAS WRONG STREET NAMES.
 MONGOMERY WAY AND PLACE ARE INCORRECT.
 PLEASE REVISE AS NECESSARY.
  
 2) PLEASE INDICATE ON PLANS THAT THE
 PARKING GARAGE IS EITHER CONSIDERED
 AN OPEN OR CLOSED PARKING GARAGE.
  
 3) PLEASE INDICATE THE EXISTING TWO
 MEANS OF EGRESS IN THE PARKING GARAGE
 ON SP-2.
  
 4) PLEASE INDICATE FIRE RATINGS OF
 NEW STAIRWELL DOORS FOR LEVELS J & K.
 ALSO PLEASE INDICATE SELF-CLOSING
 DEVICES WILL BE PRESENT.
  
 5) STAIRWELL SIGNS ARE REQUIRED
 INDICATING THE STAIR #, TERMINUS AT
 THE TOP OR BOTTOM, ETC. ALSO TACTILE
 SIGNAGE IS REQUIRED AT STAIR DOOR
 OPENINGS.
  
 6) PLAN SHEET MP-2 INDICATES "ADD FIRE
 DEPARTMENT CONNECTION". DO YOU NOT
 MEAN HOSE VALVES INSTEAD OF FDC"S.
 FDC'S ARE CONNECTED TO PUMP TO THE
 SYSTEM, NOT CONNECT HOSES TO FIGHT
 FIRES.
  
 7) PLEASE SHOW EMERGENCY LIGHTING
 EQUIPMENT IN STAIRWELLS AND NEW FLOOR
 LOCATIONS.
  
 8) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHERS.
  
 9) PLEASE INDICATE IF THE GARAGE IS
 SPRINKLER PROTECTED OR NOT.
  
 10) PLEASE SEE COMMON PATH OF TRAVEL
 NOTE BY BUILDING PLAN REVIEWER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910