Plan Review Notes
Plan Review Notes For Permit 03081533
Permit Number 03081533
Review Stop B
Sequence Number 1
Notes
Date Text
2003-09-10 00:00:00THIS IS A THRESHOLD BUILDING AND WILL
 REQUIRE A THRESHOLD INSPECTION PLAN,
 THRESHOLD INSPECTOR AND THE STATEMENT
 ON THE PLANS AS PROVIDED FOR IN FBC 105.
 13.4.4.
  
 FBC 3401.4 REQUIRES THE ENTIRE BUILDING
 BE ALTERED TO MEET THE CODE WHEN THE
 HEIGHT IS INCREASED.
  
 THE NOTES ON SHEET A3 REFERENCE THE
 1994SBC.FLORIDA IS CURRENTLY USING
 THE 2001 FLORIDA BUILDING CODE WITH THE
 JUNE 2003 REVISIONS.PLEASE REVISE AS
 NECESSARY AND ENSURE COMPLIANCE WITH
 SAME.ALSO, SEE FBC 104.2.1 REGARDING
 QUOTING CODE SECTIONS NOT BEING
 ACCEPTABLE FOR SPECIFIC DESIGN
 INFORMATION.
  
 THE COMMON PATH OF TRAVEL TO THE EXIT
 EXCEEDS THE 50' ALLOWED BY FBC 1027.6.3.
 PLEASE REVISE AS NECESSARY.
  
 PLEASE PROVIDE SKETCHES AND
 CALCULATIONS DEMONSTRATING THAT THE
 PROPOSED AND EXISTING PORTIONS OF THE
 GARAGE MEETS ONE OF THE METHODS FOR AN
 OPEN PARKING GARAGE IN ACCORDANCE WITH
 FBC 411.3.2 OR COMPLY WITH FBC 411.4
 FOR AN ENCLOSED GARAGE.
  
 SHOW THE CLEAR HEIGHT OF THE GARAGE
 THROUGHOUT OF AT LEAST 7'.SEE FBC
 411.2.2.
  
 PROVIDE THE VERTICAL ACCESSIBILITY IN
 ACCORDANCE WITH FBC 11-4.1.5.SEE ALSO
 FBC 11-4.6.2.
  
 THE STRUCTURAL PLANS DO NOT SHOW ANY
 DETAILS OR DIMENSIONS FOR THE WALL
 OPENINGS.
  
 PLEASE PROVIDE STRUCTURAL COMPUTATIONS
 AND THE METHOD OF INVESTIGATION USED
 DEMONSTRATING THAT THE EXISTING
 STRUCTURE WILL SUPPORT THE ADDED
 BUILDING AREA AND MEETS THE CURRENT
 CODE.