| 2003-09-10 00:00:00 | THIS IS A THRESHOLD BUILDING AND WILL |
| | REQUIRE A THRESHOLD INSPECTION PLAN, |
| | THRESHOLD INSPECTOR AND THE STATEMENT |
| | ON THE PLANS AS PROVIDED FOR IN FBC 105. |
| | 13.4.4. |
| | |
| | FBC 3401.4 REQUIRES THE ENTIRE BUILDING |
| | BE ALTERED TO MEET THE CODE WHEN THE |
| | HEIGHT IS INCREASED. |
| | |
| | THE NOTES ON SHEET A3 REFERENCE THE |
| | 1994SBC.FLORIDA IS CURRENTLY USING |
| | THE 2001 FLORIDA BUILDING CODE WITH THE |
| | JUNE 2003 REVISIONS.PLEASE REVISE AS |
| | NECESSARY AND ENSURE COMPLIANCE WITH |
| | SAME.ALSO, SEE FBC 104.2.1 REGARDING |
| | QUOTING CODE SECTIONS NOT BEING |
| | ACCEPTABLE FOR SPECIFIC DESIGN |
| | INFORMATION. |
| | |
| | THE COMMON PATH OF TRAVEL TO THE EXIT |
| | EXCEEDS THE 50' ALLOWED BY FBC 1027.6.3. |
| | PLEASE REVISE AS NECESSARY. |
| | |
| | PLEASE PROVIDE SKETCHES AND |
| | CALCULATIONS DEMONSTRATING THAT THE |
| | PROPOSED AND EXISTING PORTIONS OF THE |
| | GARAGE MEETS ONE OF THE METHODS FOR AN |
| | OPEN PARKING GARAGE IN ACCORDANCE WITH |
| | FBC 411.3.2 OR COMPLY WITH FBC 411.4 |
| | FOR AN ENCLOSED GARAGE. |
| | |
| | SHOW THE CLEAR HEIGHT OF THE GARAGE |
| | THROUGHOUT OF AT LEAST 7'.SEE FBC |
| | 411.2.2. |
| | |
| | PROVIDE THE VERTICAL ACCESSIBILITY IN |
| | ACCORDANCE WITH FBC 11-4.1.5.SEE ALSO |
| | FBC 11-4.6.2. |
| | |
| | THE STRUCTURAL PLANS DO NOT SHOW ANY |
| | DETAILS OR DIMENSIONS FOR THE WALL |
| | OPENINGS. |
| | |
| | PLEASE PROVIDE STRUCTURAL COMPUTATIONS |
| | AND THE METHOD OF INVESTIGATION USED |
| | DEMONSTRATING THAT THE EXISTING |
| | STRUCTURE WILL SUPPORT THE ADDED |
| | BUILDING AREA AND MEETS THE CURRENT |
| | CODE. |