Plan Review Notes
Plan Review Notes For Permit 03081504
Permit Number 03081504
Review Stop M
Sequence Number 1
Notes
Date Text
2003-09-24 00:00:00DENIED:
 PLEASE CLARIFY AIR MAKE UP FOR THE
 ELECTRICAL ROOM.PLAN SHEET AM-1
 INDICATES AN EXHAUST FAN RATED AT 400
 CFM, INDICATE WHERE THE MAKE-UP AIR
 WILL BE PROVIDED.PLAN SHEET A.A-1
 DOES NOT INDICATE ANY LOUVERED DOORS
 OR LOUVERS TO ACCOMMODATE FOR THE AIR
 MAKE UP.
  
 SEE ALSO COMMENT BY BUILDING, HEIGHT
 REQUIREMENT FOR THE CURB TO THE EXHAUST
 FAN.