| Plan Review Notes For Permit 03081504 |
| Permit Number |
03081504 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-24 00:00:00 | DENIED: | | | PLEASE CLARIFY AIR MAKE UP FOR THE | | | ELECTRICAL ROOM.PLAN SHEET AM-1 | | | INDICATES AN EXHAUST FAN RATED AT 400 | | | CFM, INDICATE WHERE THE MAKE-UP AIR | | | WILL BE PROVIDED.PLAN SHEET A.A-1 | | | DOES NOT INDICATE ANY LOUVERED DOORS | | | OR LOUVERS TO ACCOMMODATE FOR THE AIR | | | MAKE UP. | | | | | | SEE ALSO COMMENT BY BUILDING, HEIGHT | | | REQUIREMENT FOR THE CURB TO THE EXHAUST | | | FAN. |
|