| Plan Review Notes For Permit 03081504 |
| Permit Number |
03081504 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-02 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR | | | INFORMATION REQ'DON TITLE BLOCK. | | | PLEASE PROVIDE CERTIFICATE/AUTH #. | | | | | | 2)NOTE: PLANS NOTE ON AES-2 TO SEE RISER | | | FOR SERV. BAY BLDG? PLEASE CLARIFY | | | WHERE THIS RISER IS SHOWN? | | | 215.5 | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% PER 215.3, 230.42 ETC. | | | | | | PLEASE NOTE:: AS PER LOCAL AMENDMENTS: | | | COLOR CODING OF FEEDERS FOR 277/480V | | | IS BR/PURP/YELLOW.215 LOCAL. | | | JUSTA NOTE;NOT REQ'D ON THIS SYSTEM | | | BEING 120/208V | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|