2003-08-28 00:00:00BUILDING PLAN REVIEW
 PERMIT:03081504
 ADD: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK CORP
 TEL: (954)444-2995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) ENTRY DOOR
 B) ROOFING ASSEMBLY
  
 3) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 4)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE ROOF FRAMING PLAN INDICATES THE USE
 OF 3/4" A. B. @ 30" O. C., THERE IS NO
 LENGHT GIVEN?
  
 6)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
 NO INFORMATION ON THE ROF TOP EXHAUST
 FAN?
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026