| Plan Review Notes For Permit 03081449 |
| Permit Number |
03081449 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-29 00:00:00 | ************ NOTES REDLINED ****** | | | | | | PLEASE SEE MISSING EQUIPMENT GRND FROM | | | MAIN TO PANEL, SIZE PER 250.122 | | | 250.24/250.110 | | | | | | PLEASE SEE RANGE SHOWN W/ 2P30A? SHOULD | | | BE 50A. | | | | | | PLEASE MOVE ADDTIONAL SD OUTSIDE MASTER | | | BEDROOM. NFPA-72 8-1.4.2 | | | | | | PLEASE SEE THAT MAIN IS NOT SHOWN ON | | | PLANS AS SHOWN ON RISER. | | | | | | | | | REVISE PLANS BEFORE ROUGH. |
|