| Plan Review Notes For Permit 03081448 |
| Permit Number |
03081448 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-02 00:00:00 | PROVISO: | | | | | | 1.PLANS ARE DIFFICULT TO READ SOME OF | | | THE DUCT SIZES.PLEASE SUBMIT REVISED | | | PLAN INDICATING THE CORRECT DUCT SIZE. | | | | | | 2.BALANCE AIR RETURN - RETURN TRANSFER | | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM ITS SERVING & THE | | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. | | | | | | 3.PLEASE PROVIDE AUXILIARY DRAIN PANS | | | UNDER AHU # 2 & 3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|