Date Text
2003-09-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT PO.1 DOMESTIC WATER ISOMETRIC,
 FILTERS SHALL COMPLY WITH NSF STANDARDS.
 MANUF. SPECIFICATION SHEET REQUIRED.
 2) WATER HAMMER ARRESTORS SHALL BE LOCA-
 TED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-
 WH 201 AND MANUF. INSTALL. INSTR. (#13)
 3) SHT PO.1 SANITARY RISER DIAGRAM, SHOW
 LOCATION OF TIE IN FOR LAV IN WOMEN'S
 TOILET ROOM.
  