| Plan Review Notes For Permit 03081413 |
| Permit Number |
03081413 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-09 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-REVISE SURVEY TO MATCH FLOOR PLANS. | | | SEE MASTER BEDROOM. | | | 2-GLASS BLOCK AT BATHROOM TO BE SAFETY | | | GLASS IF FACE THICKNESS IS LESS THAN | | | 0.25". SEC. 2405.2 FBC 2001. | | | 3-UPDATE TRUSS ANCHOR SCHEDULE TO COMPLY | | | WITH SECTION 1609.4.3 FBC 2001. USE | | | USP 2003 CATALOGUE OR SIMPSON HIGH | | | WIND-RESISTANT CONSTRUCTION CATALOGUE. | | | 2003 WHICH ARE THE ONLY ONES BEING | | | UPDATED. | | | **NOTE:USE SAME FASTENER TYPE AND NUMBER | | | AS PUBLISHED OR PROVIDE ENGINEERING | | | CALCULATIONS WHEN FASTENERS DO NOT | | | MATCH THOSE ON CATALOGUES. | | | 4-REVISE SPECIFICATIONS FOR INSTALLATION | | | OF CEILING AT FRONT AND REAR PORCH. | | | SEE ASTM C-1063 FOR PROPER NAIL SIZE. | | | SEC. 2504.2 FBC 2001. |
|