| 2003-09-17 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-SURVEY HAS INCORRECT/INCOMPLETE INFO. |
| | A)LEGAL DESCRIPTION: FILL IN INFORMATION |
| | AND THIS IS PALM BEACH COUNTY, NOT |
| | MARTIN COUNTY. |
| | B)SURVEYOR'S NOTES: NEED COMNPLETE AND |
| | CORRECT INFORMATION ON ITEM #3. |
| | **ITEM #9: REVISE ADDRESS. THIS IS WEST |
| | PALM BEACH, NOT PALM BEACH COUNTY. |
| | **ITEM #10: WPB USES MAP DATED MARCH 1ST |
| | 1979. REVISE MAP AND PANEL # AS REQ'D. |
| | C)BUILDING FOOTPRINT DOESN'T MATCH |
| | FLOOR PLANS. REVISE AS REQUIRED. |
| | |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-PROVIDE AIR HANDLER UNIT COMPLETE |
| | HANGING DETAILS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 4-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS AND SEC. 2405.2 FBC 2001. |
| | 5-PRIVACY WALL SECTION DETAIL: SPECIFY |
| | VERTICAL REINFORCEMENT AND ATTACHMENT |
| | TO CANTILEVERED FOOTING. SECTION |
| | 104.2.1.2 CITY AMENDEMNTS TO FBC 2001. |
| | 6-PROVIDE CALCULATIONS FOR UPLIFT LOADS |
| | AT REAR COVERED PORCH CONCRETE PADS. |
| | SEC. 1606.1.3 FBC 2001 AND SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-PROVIDE COMPLETE DETAIL/SECTION THRU |
| | BAY WINDOW AT CAFE AREA. PROVIDE |
| | SPECS FOR CANTILEVERED BEAM AND THE |
| | ATTACHMENT TO COLUMNS. ALSO, PROVIDE |
| | DETAIL AT INTERSECTION OF COVERED |
| | PORCH BEAM, CAFE BAY WINDOW BEAM AND |
| | LANAI BEAM. SECTION 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 8-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| | DETAILS THAT ARE AFFECTED BY SECTION |
| | 1609.4.3 FBC 2001, WHICH DOES NOT |
| | ALLOW STEEL STRESS TO BE INCREASED. |
| | **NOTE: USE SIMPSON HIGH WIND-RESISTANT |
| | CONSTRUCTION CATALOGUE WHICH HAVE THE |
| | REVISED VALUES. |
| | 9-SPECIFY WASHERS FOR GARAGE STRUCTURAL |
| | BUCK DETAIL. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 10-PROVIDE COMPLETE DETAIL/SPECS FOR |
| | CEILING INSTALLATION AT FRONT AND |
| | REAR PORCHES. SPECIFY ALL MATERIALS |
| | AND FASTENER TYPE AND SPACING. SEE |
| | ASTM C-926 AND ASTM C-1063. |
| | SEC. 2504.2 FBC 2001. |
| | 11-PROVIDE COMPLETE INFORMATION ON TOP |
| | OF ENERGY CALCULATIONS FORM. |
| | 12-STORM SHUTTERS: CLEARLY MARK ON DWGS |
| | SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| | TYPE AND SPACING TO BE USED ACCORDING |
| | TO THE DESIGN PRESSURES, PANEL SPAN, |
| | EDGE DISTANCE, CONNECTION TYPE AND |
| | STRUCTURE TO BE ATTACHED TO. |
| | 13-SITE SPECIFIC PRODUCT APPROVAL FOR |
| | BUTT GLAZING SYSTEM: A)PANEL TESTED |
| | HAS THREE PANELS. PANEL SHOWN ON PLANS |
| | HAS 4 PANELS. PROVIDE COMPLETE ENGINEE |
| | RING ANALYSIS FOR PROPOSED SYSTEM. |
| | SEC. 2406.1 AND 2406.2 FBC 2001. |
| | **NOTE: TEST DOESN'T SPECIFY EDITION |
| | OF ASTM E330. NEED TO USE THE CRITERIA |
| | SET ON ASTM E330-84 EDITION WHICH IS |
| | THE ONE REFERENCED IN THE FBC. |
| | **PROVIDE ORIGINAL SEALED, SIGNED AND |
| | DATED TEST REPORTS AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES. |
| | **PRODUCT APPROVAL SUBMITTED IS FOR |
| | 4500 SERIES STOREFRONT SYSTEM. PRODUCT |
| | APPROVAL FORM CALLS FOR 4000 SERIES. |
| | CLARIFY AS REQUIRED. |
| | **PRODUCT APPROVAL FORM DOESN;T SPECIFY |
| | THICKNESS FOR 1200 TYPE SILICONE. |
| | |
| | 14-OWES $6.81 FOR UPDATED VALUATION. |