Plan Review Notes
Plan Review Notes For Permit 03081355
Permit Number 03081355
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-26 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE PLANS TO COMPLY WITH THE
 FOLLOWING CODE ARTICLES AND RESUBMIT
 FOR REVIEW.
  
 1} PLEASE NOTE THAT THE OCP FOR THE AHU
 IS INCORRECT FOR THE 7500 VA LOAD
 SERVED,EVEN @125%,SEE 240.6.
  
 2} PLEASE SHOW KITCHEN RECEPTACLES PER
 210.8(B).
  
 3} THE EMERGENCY LIGHTING MUST COMPLY
 WITH 700.12(E),"LIGHTING IN THE AREA".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718