| Plan Review Notes For Permit 03081355 |
| Permit Number |
03081355 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-26 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE REVISE PLANS TO COMPLY WITH THE | | | FOLLOWING CODE ARTICLES AND RESUBMIT | | | FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT THE OCP FOR THE AHU | | | IS INCORRECT FOR THE 7500 VA LOAD | | | SERVED,EVEN @125%,SEE 240.6. | | | | | | 2} PLEASE SHOW KITCHEN RECEPTACLES PER | | | 210.8(B). | | | | | | 3} THE EMERGENCY LIGHTING MUST COMPLY | | | WITH 700.12(E),"LIGHTING IN THE AREA". | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|