| 2003-08-29 00:00:00 | PROVISO: | | | THE MECHANICAL FLOOR PLAN IS REVERSED | | | OF THE BUILDING FLOOR PLAN. | | | | | | RETURN AIR SHALL BE CALCULATED AS | | | FOLLOWS: | | | BALANCE AIR RETURN - RETURN TRANSFER | | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM IT'S SERVING & THE | | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. |
|