| Date |
Text |
| 2003-09-08 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SIGNED AND SEALED COPY OF |
| | THE SOIL BORING TEST REPORT AS REQUIRED |
| | BY FBC 1804.2.2. |
| | |
| | 4) SPECIFY THE FASTENERS AND EMBED DEPTH |
| | FOR THE TRUSS BUCKETS (ST) ON A7. |
| | |
| | 5) SPECIFY THE FASTENERS AND EMBED DEPTH |
| | FOR THE STEEL COLUMN BASES ON A7. |
| | |
| | 6) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | 3/4" DIA. WEDGE ANCHORS IN DETAIL 1 ON |
| | A8. |
| | |
| | 7) THE ANCHOR SCHEDULE ON A7 SPECIFIES |
| | (9) 10D X 1-1/2" NAILS FOR THE TA9 |
| | CONNECTORS(USP TA20R). THIS IS INCORRECT |
| | THE 2003 USP CATALOG REQUIRES (10) 10D X |
| | 1-1/2" NAILS TO ATTAIN THE LISTED VALUES |
| | PLEASE CORRECT. |
| | |
| | 8)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 9) THE SITE SPECIFIC PRODUCT APPROVAL |
| | SUBMITTED IS FOR INSWING DOORS AND IS |
| | LIMITED TO A MAXIMUM HEIGHT OF 6'8". THE |
| | GLAZED DOUBLE ENTRY DOORS ARE OUTSWING |
| | AND ARE 8' IN HEIGHT. THE FORM IS ALSO |
| | REQUIRED TO BE SIGNED BY THE DESIGNER OF |
| | RECORD. |
| | |
| | 10) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR ROOFING MATERIALS. |
| | |
| | 11) SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SUBMIT A |
| | SIGNED AND SEALED LETTER FROM KNEZEVICH |
| | AND ASSOC. CLARIFYING THE USE OF CALK-IN |
| | ANCHORS IN CONCRETE BLOCK. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |