| 2003-09-04 00:00:00 | 1) FIRE ALARM NOTES # 17 INDICATES | | | A SUPERVISORY SIGNAL WHEN DUCT | | | SMOKE DETECTORS ARE ACTIVATED. ALARM | | | SIGNALS ALLOWED ONLY. | | | | | | 2) FIRE ALARM NOTES # 19 INCORRECT. | | | FIRE ALARM CIRCUITS SHALL BE CLASS A, | | | STYLE D. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM REMODEL. | | | | | | 4) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLER REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|