| Plan Review Notes For Permit 03081252 |
| Permit Number |
03081252 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-05 00:00:00 | 1) FIRE ALARM NOTES # 19 IS INCORRECT. | | | FIRE ALARM CIRCUITS SHALL BE CLASS A, | | | STYLE D. | | | | | | 2) FIRE ALARM NOTES # 17 IS INCORRECT. | | | DUCT SMOKE DETECTORS WHEN ACTIVATED | | | SHALL ACTIVATE THE BUILDING'S FIRE | | | ALARM SYSTEM NOT A SUPERVISORY | | | SIGNAL. | | | | | | 3) SEPARATE PLANS AND PERMITS FOR | | | FIRE SPRINKLER AND FIRE ALARM SYSTEM | | | REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|