Plan Review Notes
Plan Review Notes For Permit 03081239
Permit Number 03081239
Review Stop P
Sequence Number 3
Notes
Date Text
2004-01-14 00:00:00DENIED
 REFERNECE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A) COMMENTS FROM FIRST REVIEW AND SECOND
 REVIEW HAVE NOT BEEN ADDRESSED, ANSWERED
 OR RESPONSE HAS NOT BEEN FOUND. COMMENT
 NUMBER TO REMAIN THE SAME AS FIRST AND
 SECOND REVIEW FOR CLAIRITY.
 5) OIL/SAND INTERCEPTOR SHALL BE SIZED
 BY RODNEY COMPO, ENVIRONMENTAL COMPLIAN-
 CE. WASTE ORD; #2938-96. (561) 837-4074.
 (NO INFORMATION RECIEVED TO DATE)
 7) MSDS SHEETS TO BE SUBMITTED. NO RES-
 PONSE TO THIS REQUEST FOR SECOND REVIEW.
 INDICATED THAT AN EYE WASH/EMERGENCY
 SHOWER IS REQUIRED PER MSDS SHEETS SUB-
 MITTED FOR SOLVENT. SEC 411
 8) SUBMIT DETAILS FOR ACCESSIBLE TOILET
 ROOM. NO DETAILS FOR ACCESSIBLE SHOWER
 HAVE BEEN SUBMITTED. 11-4.21 AND ALL
 SUBSECTIONS.
 1B) THERMAL EXPANSION CONTROL REQUIRED
 PER SECTION 607.3.2
 ****NEW COMMENT****
 1C) A-4.0 HAND DRAWN CORRECTIONS NOT
 APPROVED. (SEE DRINKING FOUNTAIN). MAKE
 CORRECTIONS ON NEW SIGNED/SEALED SHEET
 FOR REVIEW.
 2C) SHT A-2.1 SANITARY RISER DIAGRAM.
 SEE RED LINE CORRECTION IN BATHROOM.
 SECTION 909.1 WET VENT. FIXTURES OTHER
 THAN WET VENTED FIXTURES SHALL CONNECT
 DOWNSTREAM OF BATHROOM FIXTURES.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]