| Date |
Text |
| 2004-01-14 00:00:00 | DENIED |
| | REFERNECE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | A) COMMENTS FROM FIRST REVIEW AND SECOND |
| | REVIEW HAVE NOT BEEN ADDRESSED, ANSWERED |
| | OR RESPONSE HAS NOT BEEN FOUND. COMMENT |
| | NUMBER TO REMAIN THE SAME AS FIRST AND |
| | SECOND REVIEW FOR CLAIRITY. |
| | 5) OIL/SAND INTERCEPTOR SHALL BE SIZED |
| | BY RODNEY COMPO, ENVIRONMENTAL COMPLIAN- |
| | CE. WASTE ORD; #2938-96. (561) 837-4074. |
| | (NO INFORMATION RECIEVED TO DATE) |
| | 7) MSDS SHEETS TO BE SUBMITTED. NO RES- |
| | PONSE TO THIS REQUEST FOR SECOND REVIEW. |
| | INDICATED THAT AN EYE WASH/EMERGENCY |
| | SHOWER IS REQUIRED PER MSDS SHEETS SUB- |
| | MITTED FOR SOLVENT. SEC 411 |
| | 8) SUBMIT DETAILS FOR ACCESSIBLE TOILET |
| | ROOM. NO DETAILS FOR ACCESSIBLE SHOWER |
| | HAVE BEEN SUBMITTED. 11-4.21 AND ALL |
| | SUBSECTIONS. |
| | 1B) THERMAL EXPANSION CONTROL REQUIRED |
| | PER SECTION 607.3.2 |
| | ****NEW COMMENT**** |
| | 1C) A-4.0 HAND DRAWN CORRECTIONS NOT |
| | APPROVED. (SEE DRINKING FOUNTAIN). MAKE |
| | CORRECTIONS ON NEW SIGNED/SEALED SHEET |
| | FOR REVIEW. |
| | 2C) SHT A-2.1 SANITARY RISER DIAGRAM. |
| | SEE RED LINE CORRECTION IN BATHROOM. |
| | SECTION 909.1 WET VENT. FIXTURES OTHER |
| | THAN WET VENTED FIXTURES SHALL CONNECT |
| | DOWNSTREAM OF BATHROOM FIXTURES. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |