Plan Review Notes
Plan Review Notes For Permit 03081239
Permit Number 03081239
Review Stop M
Sequence Number 2
Notes
Date Text
2003-12-04 00:00:00DENIED:
  
 1.PLEASE PROVIDE OUTSIDE AIR CALCS FOR
 ALL AREAS, PER 2001 FBC(M) TABLE 403.3
  
 2.PLEASE CLARIFY VENTILATION FOR THE
 GARAGE AND WORK AREA. REFERENCE TABLE
 403.3 &CHAPTER 5 OF THE 2001 FBC(M)
 FOR REQUIREMENTS.
  
 3.PROVIDE MANUFACTURER INFORMATION ON
 ANY EXHAUST FANS THAT MAY BE INSTALLED.
  
 4.INDICATE WHAT TYPE OF WORK WILL BE
 DONE IN THE WORK & GARAGE AREAS -
 OUTLETS ARE INDICATED ON PLAN SHEET MEP1
 FOR WELDER, COMPRESSOR, LIFT.WILL
 ANY TYPE OF PAINTING BE DONE?
  
 5.PROVIDE INFORMATION ON STORAGE OF
 ANY HAZARDOUS MATERIALS.(MSDS SHEETS
 PROVIDED)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.