2003-11-06 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR STILL MUST BE SIZED PER 250.66
 SERVICE ENTRANCE CONDUCTORS ARE SHOWN
 AS 600MCM. SEE 250.66, MIN 1/0 FOR 600MC
 M'S.
  
 2)NOTE: PLEASE SEE OCP FOR AHU, NOW IS
 SHOWN AS 50A. PLEASE SEE LOAD IS 5KW,
 424.3B REQUIRES A MIN OCP OF 125% ,
 HOWEVER 50A OCP FOR 5KW IS TOO HIGH.
 PLEASE SEE MAX OF 150%.
  
 3)NOTE: PLEASE NOTE: PLEASE SEE AIC
 RATING IS NOW SHOWN AT 100,000 FOR ALL
 BRKRS. PLEASE VERIFY THIS, PLEASE BE
 SURE BRANCH BRKRS ARE AVAILABLE FOR THIS
 RATING. THIS RATING FOR MAIN MAY BE
 CORRECT,HOWEVER PANEL MENTIONS FOR ALL
 BREAKERS?? PLEASE CHECK W/ MANUFACTURE
 AND ALSO MAY WANT TO VERIFY COST IF
 AVAILABLE.
 110.9/215.5
  
 4)NOTE: PLEASE SEE TOP OF PANEL SCHEDULE
 SHOWS "AMPS" FOR LOADS THAT SHOULD BE
 SHOWN AS WATTS AND OR KVA? (MISPRINT)?
 PLEASE
  
 NEW NOTE:
 SINCE LAST REVIEW WE HAVE BEEN INFORMED
 BY THE ARCH/ENGINEERING BOARDS THAT
 PLANS THAT ARE SIGNED AND SEALED REQUIRE
 A "SIGNATURE" VISABLE WITH A MIN OF
 NAME ON SAID SEAL VISABLE. INITIALS ARE
 NOT PERMITTED PER FS 481.221 AND 471.025
 PLEASE SIGN WITH A SIG OF NAME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  