| 2003-11-06 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | CONDUCTOR STILL MUST BE SIZED PER 250.66 |
| | SERVICE ENTRANCE CONDUCTORS ARE SHOWN |
| | AS 600MCM. SEE 250.66, MIN 1/0 FOR 600MC |
| | M'S. |
| | |
| | 2)NOTE: PLEASE SEE OCP FOR AHU, NOW IS |
| | SHOWN AS 50A. PLEASE SEE LOAD IS 5KW, |
| | 424.3B REQUIRES A MIN OCP OF 125% , |
| | HOWEVER 50A OCP FOR 5KW IS TOO HIGH. |
| | PLEASE SEE MAX OF 150%. |
| | |
| | 3)NOTE: PLEASE NOTE: PLEASE SEE AIC |
| | RATING IS NOW SHOWN AT 100,000 FOR ALL |
| | BRKRS. PLEASE VERIFY THIS, PLEASE BE |
| | SURE BRANCH BRKRS ARE AVAILABLE FOR THIS |
| | RATING. THIS RATING FOR MAIN MAY BE |
| | CORRECT,HOWEVER PANEL MENTIONS FOR ALL |
| | BREAKERS?? PLEASE CHECK W/ MANUFACTURE |
| | AND ALSO MAY WANT TO VERIFY COST IF |
| | AVAILABLE. |
| | 110.9/215.5 |
| | |
| | 4)NOTE: PLEASE SEE TOP OF PANEL SCHEDULE |
| | SHOWS "AMPS" FOR LOADS THAT SHOULD BE |
| | SHOWN AS WATTS AND OR KVA? (MISPRINT)? |
| | PLEASE |
| | |
| | NEW NOTE: |
| | SINCE LAST REVIEW WE HAVE BEEN INFORMED |
| | BY THE ARCH/ENGINEERING BOARDS THAT |
| | PLANS THAT ARE SIGNED AND SEALED REQUIRE |
| | A "SIGNATURE" VISABLE WITH A MIN OF |
| | NAME ON SAID SEAL VISABLE. INITIALS ARE |
| | NOT PERMITTED PER FS 481.221 AND 471.025 |
| | PLEASE SIGN WITH A SIG OF NAME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |