| 2003-09-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMIN. CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SECTION 403.2 WHERE PLUMBING FIXTURES |
| | ARE REQUIRED, SEPARATE FACILITIES SHALL |
| | BE PROVIDED FOR EACH SEX. |
| | 2) SUBMIT CALCULATIONS FOR MINIMUM FAC- |
| | ILITIES. PER TABLES 1003.1 (BLDG) AND |
| | 403.1 (PLUMB) |
| | 3) SHTS A-2.0 & A-2.1 SANITARY RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | MOP SINK NOT SHOWN ON FLOOR PLAN. SEC. |
| | 104.2.1 |
| | 4) RPZ BACKFLOW PREVENTER REQUIRED ON |
| | WATER SERVICE. SEC 608.13.2 |
| | 5) OIL SEPARATOR SHALL BE SIZED BY RON- |
| | NEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| | WASTE ORD. 2938-96. (561) 837-4074. |
| | 6) SUBMIT A WATER RISER DIAGRAM. SHOW |
| | ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS ECT. SEC 104.3.1.1 |
| | 7) SUBMIT MSDS SHEETS FOR ANY HAZARDOUS |
| | MATERIALS. INDICATE AMOUNTS OF MATERIALS |
| | STORED. INFORMATION RECIEVED MAY ADD NEW |
| | COMMENTS CONCERNING AN EYE WASH OR AN |
| | EMERGENCY SHOWER. 104.2.1 |
| | 8) SUMBIT DETAILS FOR ACCESSIBLE TOILET |
| | ROOMS PER SECTION 11-4.22, 11-4.16, 11-4 |
| | .19, & 11-4.21 AND ALL SUBSECTIONS. |
| | CLEAR FLOOR SPACE - GRAB BARS - HEIGHTS |
| | & CLEARANCES, SEAT HEIGHT, SHOWER UNIT - |
| | CENTER OFF WALLS - CONTROL AREA - ECT. |
| | 9) WATER COOLER SHALL BE ARI-1010 COMP- |
| | LIANT. SUBMIT MANUF. SPECIFICATION |
| | SHEETS. |
| | 10) ALL SHEETS SHALL BE SIGNED, SEALED, |
| | AND DATED PER 61G1-16.003 |
| | 11) SUBMIT A DETAIL FOR BREAK ROOM SINK |
| | PER 11-4.24 AND ALL SUBSECTIONS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |