2003-09-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SECTION 403.2 WHERE PLUMBING FIXTURES
 ARE REQUIRED, SEPARATE FACILITIES SHALL
 BE PROVIDED FOR EACH SEX.
 2) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES. PER TABLES 1003.1 (BLDG) AND
 403.1 (PLUMB)
 3) SHTS A-2.0 & A-2.1 SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 MOP SINK NOT SHOWN ON FLOOR PLAN. SEC.
 104.2.1
 4) RPZ BACKFLOW PREVENTER REQUIRED ON
 WATER SERVICE. SEC 608.13.2
 5) OIL SEPARATOR SHALL BE SIZED BY RON-
 NEY COMPO, ENVIRONMENTAL COMPLIANCE.
 WASTE ORD. 2938-96. (561) 837-4074.
 6) SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ECT. SEC 104.3.1.1
 7) SUBMIT MSDS SHEETS FOR ANY HAZARDOUS
 MATERIALS. INDICATE AMOUNTS OF MATERIALS
 STORED. INFORMATION RECIEVED MAY ADD NEW
 COMMENTS CONCERNING AN EYE WASH OR AN
 EMERGENCY SHOWER. 104.2.1
 8) SUMBIT DETAILS FOR ACCESSIBLE TOILET
 ROOMS PER SECTION 11-4.22, 11-4.16, 11-4
 .19, & 11-4.21 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE - GRAB BARS - HEIGHTS
 & CLEARANCES, SEAT HEIGHT, SHOWER UNIT -
 CENTER OFF WALLS - CONTROL AREA - ECT.
 9) WATER COOLER SHALL BE ARI-1010 COMP-
 LIANT. SUBMIT MANUF. SPECIFICATION
 SHEETS.
 10) ALL SHEETS SHALL BE SIGNED, SEALED,
 AND DATED PER 61G1-16.003
 11) SUBMIT A DETAIL FOR BREAK ROOM SINK
 PER 11-4.24 AND ALL SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]