| Plan Review Notes For Permit 03081239 |
| Permit Number |
03081239 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-04 00:00:00 | 1) ANOTHER EXIT SIGN IS REQUIRED TO | | | DIRECT PERSONS DOWN THE HALL TOWARDS | | | THE EXIT SIGN. | | | | | | 2) BUILDING ADDRESS REQUIRED ON | | | BUILDING. ADDITIONAL INFORMATION MAY | | | BE REQUIRED AT THE ENTRANCE TO 1300 | | | ALLENDALE TO INDICATE THE WAREHOUSE | | | HAS A DIFFERENT ADDRESS. | | | | | | 3) WALLS SEPARATING THE WORK AREA FROM | | | THE OFFICE DO NOT APPEAR TO BE | | | FIRE RATED. PLEASE SEE SECTION 8-4 | | | OF THE FLORIDA FIRE PREVENTION CODE | | | AND SECTION 704 OF THE FLORIDA | | | BUILDING CODE. PLEASE REVISE AS | | | NECESSARY. | | | | | | 4) PLANS DO NOT INDICATE LOCATIONS | | | OF ALL FIRE EXTINGUISHERS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|