| 2003-08-25 00:00:00 | FAILED: |
| | 1. PLEASE PROVIDE STORM WATER |
| | CALCULATION DUE TO THE PROPOSED CHANGES |
| | AND SHOW AS HOW THE RETENTION AREA BEING |
| | UTILIZED. STORM WATER DESIGN MUST BE PER |
| | CITY OF WPB CRITERIA. |
| | 2. OIL INTERCEPTOR MUST BE CONNECTED TO |
| | SEWER LINE,NOT TO THE STORM WATER INLET. |
| | PLEASE CALL RODNEY COMPO @ 837-4051 EXT. |
| | 4074 FOR INSTALLATION,SIZE,LOCATION & |
| | INSPECTION REQUIREMENTS. |
| | 3. A CLEAN-OUT WILL NEED TO BE INSTALLED |
| | IN THE SANITARY SEWER LATERAL, ON THE |
| | PROPERTY, AT THE BACK OF SIDEWALK IF NOT |
| | ALREADY INSTALLED. CLEAN OUT AT EVERY |
| | 75'TO 100' IS ALSO REQUIRED. INDICATE |
| | THE SIZE AND TYPE OF PIPES. |
| | 4. A GATE VALVEIN THE DOMESTIC WATER |
| | LINE TO THE PROPOSED BUILDING IS |
| | REQUIRED. |
| | 5. ANY NEW CONNECTION TO THE CITY |
| | SERVICES REQUIRES APPROVAL FROM PUBLIC |
| | UTILITIES AND ENGINEERING DEPT.659-8040 |
| | 6. FIRE HYD. MUST BE MANUFACTURED PER |
| | CITY OF WPB REQUIREMENT AND PAINTED PER |
| | SILVER BY THE MANUFACTURER, 659-8040 |
| | 7. PLEASE SHOW THE FIRE LINE CONNECTIONS |
| | AND THE PIPE SIZE AND THE TYPE. A DDCV |
| | FOR THE PRIVATE FIRE HYD. IS REQUIRED. |
| | 8. PLEASE INDICATE THE TYPE OF ASPHALT |
| | AND THICKNESS FOR THE BASE AND THE SUB- |
| | BASE. |
| | 9. ALL PARKING STALLS MUST BE PAINTED |
| | WITH DOUBLE 4" WIDE PAINT. DETAILS FOR |
| | H.C PARKING MUST BE SHOWN. |
| | 10. PLEASE SHOW GARBAGE ENCLOSURE |
| | LOCATION, IT MUST BE CONSTRUCTED AND |
| | SIZE PER CITY OF WPB REQUIREMENTS IF TO |
| | BE PICKED UP BY THE CITY. |
| | 11. ALL STANDARD DETAILS MAY BE OBTAINED |
| | FROM PUBLIC UTILITIES ENGINEERING, |
| | 659-8040. |
| | 12. ALL CALCULATIONS AND CIVIL SITE |
| | PLANS MUST BE SIGNED AND SEALED BY THE |
| | DESIGN ENGINEER. |