2003-09-02 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SEE FS 471.025 FOR ENGS.
 AND FS 481.221 FOR ARCH'S. PLANS REQ'D
 TO BE SIGNED DATED AND SEALED.
  
 2)NOTE: PLEASE SEE MAX OCP FOR 5KW AHU,
 SHOWN AS 60A.??
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS
 AHU/CU AS 1P BRKRS AND #12 AWG?
 PLEASE SEE 240/310.16
  
 4)NOTE: PLEASE SEE PLUMB COMMENTS FOR
 LOCATION OF WATER HEATER(IF ANY).
 ALSO, NEC 422.17
  
 5)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GROUNDING ELECTRODE CONDUCTOR. SEC'S
 SHOWN AS 600MCM? PLEASE CLARIFY.
  
 6)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE.
  
 7)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 8)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MCB/ PANEL ETC. 110.9/215.5
  
 9)NOTE: PLEASE SEE FAC 61G1-16.004,
 PLEASE SEE MISSING LICENSE #'S FOR ARCH
 AR# AND AA#'S . PER FS 481
  
 10)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS @125% 215.3/230.42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 ***** NOTE ****
 PLANS REFERENCE THE 99NEC, PLEASE NOTE,
 AS OF JULY 1ST, 2003 WE ARE UNDER 2002
 NEC