| Plan Review Notes For Permit 03081239 |
| Permit Number |
03081239 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-02 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE FS 471.025 FOR ENGS. | | | AND FS 481.221 FOR ARCH'S. PLANS REQ'D | | | TO BE SIGNED DATED AND SEALED. | | | | | | 2)NOTE: PLEASE SEE MAX OCP FOR 5KW AHU, | | | SHOWN AS 60A.?? | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS | | | AHU/CU AS 1P BRKRS AND #12 AWG? | | | PLEASE SEE 240/310.16 | | | | | | 4)NOTE: PLEASE SEE PLUMB COMMENTS FOR | | | LOCATION OF WATER HEATER(IF ANY). | | | ALSO, NEC 422.17 | | | | | | 5)NOTE: PLEASE SEE 250.66 FOR SIZING | | | OF GROUNDING ELECTRODE CONDUCTOR. SEC'S | | | SHOWN AS 600MCM? PLEASE CLARIFY. | | | | | | 6)NOTE: PLEASE PROVIDE CIRCUITING ON | | | PLANS AND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE. | | | | | | 7)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | | -ING OF EM/EXT LTS. | | | | | | 8)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW MCB/ PANEL ETC. 110.9/215.5 | | | | | | 9)NOTE: PLEASE SEE FAC 61G1-16.004, | | | PLEASE SEE MISSING LICENSE #'S FOR ARCH | | | AR# AND AA#'S . PER FS 481 | | | | | | 10)NOTE: PLEASE SHOW ALL CONTINUOUS | | | LOADS @125% 215.3/230.42 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | ***** NOTE **** | | | PLANS REFERENCE THE 99NEC, PLEASE NOTE, | | | AS OF JULY 1ST, 2003 WE ARE UNDER 2002 | | | NEC |
|