Plan Review Notes
Plan Review Notes For Permit 03081239
Permit Number 03081239
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03081239
 ADD: 1300 ALLENDALE ROAD
 CONT:PLAN REVIEW/ CLARK CONSTRUC
 N TEL: (561)435-5132
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) CORECTION 1999 STANDARD BUILDING
 CODE, THE STATE HAS ADOPTED THE 2001
 FLORIDA BUILDING CODE.SEE SHEETA-2.1.
  
 4) SEE COPY OF CITY ADDRESSING REQUIRE-
 MENTS, EACH BUILDING HAS ITS OWN SEPER-
 ATE ADDRESS. THIS BUILDING IS LOCATED ON
 PCN74-43-43-33-16-000-2060 WHICH FRONTS
 PARKLAND ROAD, SO THE BUILDING WILL HAVE
 A PARKLAND ROAD ADDRESS.
  
 5) STRUCTURAL STEEL BUILDING "KIRBY
 BUILDING SYSTEMS" TO HAVE ENGINEERED
 PLANS.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 7)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 8)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 9)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SWING ENTRY DOORS/ IF NOT PART OF
 BUILDING PACKAGE
 B) OVERHEAD DOORS/ IF NOT PART OF
 C) ROOFING/IF NOT PART OF
  
 10)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
  
 11) 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 12) PROVIDE THRESHOLD INFORMATION FOR
 THE ENTRY DOOR ON AN ACCESSIBLE ROUTE?
  
 13) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 14)301.13.1 GROUND MOUNTED A/C UNITS:
 GROUND-MOUNTED UNITS FOR R3 RESIDENTIAL
 APPLICATIONS MAY BE ANCHORED WITH # 14
 SCREWS WITH GASKETED WASHERS ACCORDING
 TO THE FOLLOWING:
 1) FOR UNITS WITH SIDES LESS THAN 12",
 ONE SCREW SHALL BE USED AT EACH SIDE OF
 THE UNIT.
 2) FOR UNITS BETWEEN 12" & 24", TWO
 SCREWS SHALL BE USED PER DIDE.
 3) FOR UNITS BETWEEN 24" & 36", THREE
 SCREWS SHALL BE USED PER SIDE.
 4) FOR UNITS GREATER THAN 36" OR 5 TONS
 ANCHORAGE SHALL BE DESIGN IN ACCORDANCE
 WITH 301.13. (140 MPH).
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026