Plan Review Notes
Plan Review Notes For Permit 03081234
Permit Number 03081234
Review Stop P
Sequence Number 1
Notes
Date Text
2003-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 - CSST NOT APPROVED FOR EXTERNAL GAS
 PIPING PER SECTION 403.2.4.5 -
 3. TYPE OF GAS, (LP OR NATURAL)
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]