Plan Review Notes
Plan Review Notes For Permit 03081163
Permit Number 03081163
Review Stop M
Sequence Number 1
Notes
Date Text
2003-09-15 00:00:00DENIED:
 PLEASE INDICATE SIZE OF DUCTWORK BEING
 ADDED DUE TO THE RELOCATION OF THE
 AHU.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved