| Plan Review Notes For Permit 03081163 |
| Permit Number |
03081163 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-25 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES TO | | | PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 2} CHANGES TO PLANS MUST BE MADE BY THE | | | DESIGN PROFESSIONAL.( AIR HANDLER | | | RELOCATION). | | | | | | 3} PLEASE NOTE THAT ALL PLANS | | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | | ENGINEER AND 61G1-16.004 FOR ARCH. | | | SHALL HAVE A TITLE BLOCK.SEE FAC FOR | | | REQUIREMENTS ON THE TITLE BLOCK. | | | | | | 4} PLEASE INDICATE WHERE THE PANEL IS TO | | | BE RELOCATED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|