| 2003-09-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMIN. CODE |
| | W.P.B. CITY CODE |
| | |
| | 1) SHTS C-4 & IR-1. C-4 CALLS OUT A |
| | WATER METER AND AN RPBF, BUT IR-1 CALLS |
| | OUT A WELL AND PUMP. PLEASE CLAIRFY. |
| | SECTION 104.2.1. |
| | 2) SHT A-10.7 DETAIL G10 CANOPY SCUPPER |
| | DRAIN. INDICATE THE HEIGHT OF SCUPPER |
| | DETAIL. SEC 104.2.1. |
| | 3) SHT A-10.7 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107 AND ALL SUBSECTIONS |
| | SHOW ADDED SF FOR ALL VERTICAL WALLS IN- |
| | CLUDING PARAPET. SHOW ALL ADD SF FOR ALL |
| | ROOF THAT DRAIN ONTO THE ROOF FROM ABOVE |
| | 4) SUBMIT A STORM RISER DIAGRAM. SHOW |
| | ALL PIPE SIZES AND SF AS IT ACCUMULATES. |
| | SECTION 104.2.1. |
| | 5) SHT P-3 DETAIL A6. CONDENSATE SHALL |
| | NOT DRAIN INTO THE SANITARY SEWER SYSTEM |
| | SEC 90-125(5) WPB CITY CODE. CONDENSATE |
| | SHALL DRAIN SEPARATELY OUT OF BLDG. AND |
| | TIE INTO A CATCH BASIN, DRYWELL OR STORM |
| | LINE. A RELIEF VENT IS REQUIRED ON COND. |
| | LINE AS IT EXITS THE BLDG. |
| | 6) SUBMIT A CONDENSATE A CONDENSATE |
| | RISER DIAGRAM. 104.2.1. |
| | 7) SHT P-3 DETAIL A10, WATER FILTER TO |
| | BE NSF CERTIFIED. SUBMIT MANUF. SPECIFI- |
| | CATION SHEETS. |
| | 8) 61G15-23.002(2) ENGINEERS SHALL LEG- |
| | IBLY INDICATE THEIR NAME, ADDRESS AND |
| | LICENSE NUMBER ON EACH SHEET. IF PRACT- |
| | ICING THROUGH A DULY AUTHORIZED ENGIN- |
| | EERING BUSINESS, CERTIFICATE OF AUTHOR- |
| | IZATION NUMBER IS REQUIRED. |
| | 9) LANDSCAPE/IRRIGATION SHEETS. THE PER- |
| | SONAL SEAL, SIGNATURE AND DATE OF THE |
| | ARCHITECT SHALL APPEAR ON ALL SHEETS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |