Plan Review Notes
Plan Review Notes For Permit 03081161
Permit Number 03081161
Review Stop P
Sequence Number 1
Notes
Date Text
2003-09-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 W.P.B. CITY CODE
  
 1) SHTS C-4 & IR-1. C-4 CALLS OUT A
 WATER METER AND AN RPBF, BUT IR-1 CALLS
 OUT A WELL AND PUMP. PLEASE CLAIRFY.
 SECTION 104.2.1.
 2) SHT A-10.7 DETAIL G10 CANOPY SCUPPER
 DRAIN. INDICATE THE HEIGHT OF SCUPPER
 DETAIL. SEC 104.2.1.
 3) SHT A-10.7 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 SHOW ADDED SF FOR ALL VERTICAL WALLS IN-
 CLUDING PARAPET. SHOW ALL ADD SF FOR ALL
 ROOF THAT DRAIN ONTO THE ROOF FROM ABOVE
 4) SUBMIT A STORM RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND SF AS IT ACCUMULATES.
 SECTION 104.2.1.
 5) SHT P-3 DETAIL A6. CONDENSATE SHALL
 NOT DRAIN INTO THE SANITARY SEWER SYSTEM
 SEC 90-125(5) WPB CITY CODE. CONDENSATE
 SHALL DRAIN SEPARATELY OUT OF BLDG. AND
 TIE INTO A CATCH BASIN, DRYWELL OR STORM
 LINE. A RELIEF VENT IS REQUIRED ON COND.
 LINE AS IT EXITS THE BLDG.
 6) SUBMIT A CONDENSATE A CONDENSATE
 RISER DIAGRAM. 104.2.1.
 7) SHT P-3 DETAIL A10, WATER FILTER TO
 BE NSF CERTIFIED. SUBMIT MANUF. SPECIFI-
 CATION SHEETS.
 8) 61G15-23.002(2) ENGINEERS SHALL LEG-
 IBLY INDICATE THEIR NAME, ADDRESS AND
 LICENSE NUMBER ON EACH SHEET. IF PRACT-
 ICING THROUGH A DULY AUTHORIZED ENGIN-
 EERING BUSINESS, CERTIFICATE OF AUTHOR-
 IZATION NUMBER IS REQUIRED.
 9) LANDSCAPE/IRRIGATION SHEETS. THE PER-
 SONAL SEAL, SIGNATURE AND DATE OF THE
 ARCHITECT SHALL APPEAR ON ALL SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]