Plan Review Notes
Plan Review Notes For Permit 03081161
Permit Number 03081161
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-09-05 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 3) PLEASE INDICATE LOCATIONS OF ALL
 EXISTING OR NEW FIRE HYDRANTS.
  
 4) NOTE # 1 ON C-5 INDICATES WORDING
 FOR FIRE LANE(S). PLEASE INDICATE
 LOCATIONS OF THESE SIGNS.
  
 5) CODES NOTES ON G-1 INDICATES THAT
 THE BUILDING WILL BE FIRE SPRINKLER
 PROTECTED BUT THE F.D. NOTES ON SAME
 PAGE INDICATES THE BUILDING IS NON
 FIRE SPRINKLER PROTECTED. PLEASE
 CLARIFY.
  
 6) MAGLOCKS NOTED ON VESTIBULE ENTRY
 DOORS ON PAGE C-5. PLEASE EXPLAIN
 OBVIOUS PURPOSE AND FUNCTION.
  
 7) BUILDING ADDRESS LOCATION COULD NOT
 BE SEEN ON ELEVATION DRAWING. BUILDING
 ADDRESS IS REQUIRED TO BE 6" HIGH.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 9) FIRE EXTINGUISHER(S) ARE MENTIONED
 DURING CONSTRUCTION BUT COULD NOT BE
 SEEN ON THE FINISHED FLOOR PLAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL