Plan Review Notes
Plan Review Notes For Permit 03081161
Permit Number 03081161
Review Stop E
Sequence Number 1
Notes
Date Text
2003-09-10 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE COPIES OF BOTH FAC`S
 ATTACHED, 61G15-23.002 FOR ENGINEERS AND
 61G1-16.004 FOR ARCHS. PER FS`S 471 AND
 481. PLEASE SEE MISSING LICENSE #`S
 REQUIRED ON TITLE BLOCKS FOR DESIGNERS
 OF RECORD, INCLUDING ANY FIRM LICENSE
 #'S AND/OR CERTIFICATE OF AUTHORIZATION
 #'S ALSO. PLEASE SEE THAT THIS WILL BE
 REQ'D ON AL SHEETS WHEN SUBMITTTING
 PLANS FOR PERMIT AND SUBMITTED FOR
 RECORD.
  
 2)NOTE: PLEASE SEE THAT PLANS SHOW
 REFERENCE TO THE 1999 NEC. PLEASE NOTE:
 WE ARE NOW UNDER THE 2002 NEC AS OF
 JULY 1ST, 2003. PLEASE ADJUST.
  
 3)NOTE: PLEASE CLARIFY ON E-2, DATA/ELEC
 RM APPEARS TO SHOW A TRANSFORMER ON FLR
 LAYOUT? PLEASE NOTE . THIS IS NOT SHOWN
 ON RISER AND MAY JUST BEMISPRINT?
  
 4)NOTE: PLEASE SEE NOTES TO GROUNDING
 ELECTRODE CONNECTIONS ON RISER, MENTIONS
 ATTACHED TO BLDG STEEL. PLEASE CLARIFY
 THIS AS ACTUALLY BEING FOOTER STEEL AS
 REQUIRED UNDER 250.50.
 PLEASE NOTE: ANY "BUILDING STEEL" MUST
 ALSO BE A POINT OF ATTACHMENT DEPENDING
 ON BLDG CONSTRUCTION TYPE.
  
 5)NOTE: PLEASE CLARIFY LOADS FOR TRACK
 LIGHTING. PLEASE SHOW IN LOAD CALCS
 OR BY NOTE THAT TRACK LIGHTING FIGURED
 PER 220.12B
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW MDP AND PANELS. IT IS NOTED THAT
 PANELS REFERENCE :NOTE 9: HOWEVER THIS
 IS REQUIRED AT TIME OF PLAN REVIEW AND
 APPLICATION FOR PERMIT. 110.9/ 215.5
  
 7)NOTE: PLEASE SEE THAT THIS IS JUST A
 NOTE: MDP SHOWS 100A OCP FOR SUB PANELS
 AND 3/0'S FOR CONDUCTOR SIZE ON RISER.
 IT IS UNDERSTOOD THAT THERE IS NO NEC
 VIOLATION FOR INSTALLING LARGER CONDUCT-
 ORS THAN REQ'D FOR MIN, HOWEVER, IT IS
 THE BEST OF MY KNOWLEDGE THAT 100A BRKR
 WILL ONLY ACCEPT UP TO 1/0'S?
 THIS IS JUST A NOTE AND IF 3/0'S ARE
 SHOWN THEN THEY WILL BE REQ'D TO BE
 INSTALLED. (MAC ADAPTERS) ETC. MAY BE
 USED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW WITH THE EXCEPTION OF NOTE:7.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]