| Notes |
| Date |
Text |
| 2003-08-28 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/ | | | PANELS/ PLANS. PLEASE SEE RISER SHOWS | | | A PANEL L2F? PLEASE CLARIFY WHERE THIS | | | IS ON PLANS AND PANEL SCHEDULE.215.5 | | | | | | 2)NOTE: PLEASE PROVIDE PANEL SCHEDULE | | | FOR L2A, PLEASE ALSO NOTE: | | | ALL CONTINUOUS LOADS ARE TO BE SHOWN AT | | | 125%. 215.3,230.42 ETC | | | | | | | | | PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER REVIEWERS THAT MAY HAVE AN AFFECT | | | ON ELECTRICAL PLANS, | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|