| Plan Review Notes For Permit 03081096 |
| Permit Number |
03081096 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1) SUBMIT A SANITARY AND A WATER RISER | | | ISOMETRIC DIAGRAM. 104.3.1.1 | | | 2) SUBMIT A DETAIL FOR TOILET ROOM PER | | | 11-4.22. SHOW CLEAR FLOOR SPACE FOR W/C | | | 11-16.2, LAV 11-4.19.3 AND TUB 11-4.20.2 | | | SHOW HEIGHT OF W/C 11-4.16.3, SHOW FLUSH | | | CONTROLS 11-4.16.5. W/C TO BE 1'6" OFF | | | WALL FIGURE 28. FOR LAVS SHOW HEIGHT & | | | CLEARANCE 11-4.19.3, EXPOSED PIPES AND | | | SURFACES 11-4.19.4 AND FAUCETS 11-4.19.5 | | | FOR BATHTUB SHOW GRAB BAR HEIGHT FIGS | | | 33 & 34, CONTROLS 11-4.20.5 (FIG 34) | | | 3) 61G1-16.003 THE PERSONAL SEAL, SIGNA- | | | TURE AND DATE SHALL APPEAR ON EACH SHEET | | | - NO DATE ON SHEETS. - SEE ATTACHED | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|