Plan Review Notes
Plan Review Notes For Permit 03081096
Permit Number 03081096
Review Stop P
Sequence Number 1
Notes
Date Text
2003-09-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) SUBMIT A SANITARY AND A WATER RISER
 ISOMETRIC DIAGRAM. 104.3.1.1
 2) SUBMIT A DETAIL FOR TOILET ROOM PER
 11-4.22. SHOW CLEAR FLOOR SPACE FOR W/C
 11-16.2, LAV 11-4.19.3 AND TUB 11-4.20.2
 SHOW HEIGHT OF W/C 11-4.16.3, SHOW FLUSH
 CONTROLS 11-4.16.5. W/C TO BE 1'6" OFF
 WALL FIGURE 28. FOR LAVS SHOW HEIGHT &
 CLEARANCE 11-4.19.3, EXPOSED PIPES AND
 SURFACES 11-4.19.4 AND FAUCETS 11-4.19.5
 FOR BATHTUB SHOW GRAB BAR HEIGHT FIGS
 33 & 34, CONTROLS 11-4.20.5 (FIG 34)
 3) 61G1-16.003 THE PERSONAL SEAL, SIGNA-
 TURE AND DATE SHALL APPEAR ON EACH SHEET
 - NO DATE ON SHEETS. - SEE ATTACHED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]