| Plan Review Notes For Permit 03080986 |
| Permit Number |
03080986 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-04-13 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | | REVISION.THE FLOOR PLAN DOES HOWEVER | | | REFLECT THREE AHU'S WHEREAS THE APPROVED | | | MECHANICAL PLANS INDICATE ONLY TWO.THE | | | LOCATION OF THE AHU #2 HAS ALSO CHANGED. | | | A MECHANICAL REVISION WILL BE NECESSARY. | | | | | | PLEASE INDICATE TONNAGE OF THE | | | ADDITIONAL AHU.WHAT WILL BE THE TOTAL | | | REQUIREMENT FOR AIR TO THIS SPACE? | | | ARE THE ENGERGY CALCULATIONS CORRECT OR | | | DO THEY NEED TO BE REVISED?PLEASE | | | CLARIFY THE ABOVE INFORMATION AND SUBMIT | | | REVISION FOR THE MECHANICAL CHANGES. | | | | | | PROVIDE MANUFACTURER SUBMITTAL DATA FOR | | | THE CONDENSING UNIT STANDS.PLANS DO | | | NOT REFLECT HOW THE CONDENSING UNITS | | | ARE TO BE MOUNTED.THE ARCHITECT OR | | | ENGINEER IS REQUIRED TO PROVIDE A DETAIL | | | REFLECTING HOW THE STANDS ARE TO BE | | | ATTACHED TO THE EXISTING ROOF STRUCTURE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|