Plan Review Notes
Plan Review Notes For Permit 03080986
Permit Number 03080986
Review Stop M
Sequence Number 4
Notes
Date Text
2004-04-13 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVISION.THE FLOOR PLAN DOES HOWEVER
 REFLECT THREE AHU'S WHEREAS THE APPROVED
 MECHANICAL PLANS INDICATE ONLY TWO.THE
 LOCATION OF THE AHU #2 HAS ALSO CHANGED.
 A MECHANICAL REVISION WILL BE NECESSARY.
  
 PLEASE INDICATE TONNAGE OF THE
 ADDITIONAL AHU.WHAT WILL BE THE TOTAL
 REQUIREMENT FOR AIR TO THIS SPACE?
 ARE THE ENGERGY CALCULATIONS CORRECT OR
 DO THEY NEED TO BE REVISED?PLEASE
 CLARIFY THE ABOVE INFORMATION AND SUBMIT
 REVISION FOR THE MECHANICAL CHANGES.
  
 PROVIDE MANUFACTURER SUBMITTAL DATA FOR
 THE CONDENSING UNIT STANDS.PLANS DO
 NOT REFLECT HOW THE CONDENSING UNITS
 ARE TO BE MOUNTED.THE ARCHITECT OR
 ENGINEER IS REQUIRED TO PROVIDE A DETAIL
 REFLECTING HOW THE STANDS ARE TO BE
 ATTACHED TO THE EXISTING ROOF STRUCTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.