2004-02-20 00:00:00************* UNSAT ****************
  
 PLEASE SEE REVISED PLANS ARE COMING IN
 WITH ALL NEW ELECTRICAL SERVICE ETC.
 THE FOLLOWING ARE NEW NOTES AND NOTES
 FROM ORIGINAL REVIEWS THAT WERE REDLINED
 ON ORIG PLANS.
  
 1)NOTE: PLEASE SEE NOTE #5, MENTIONS
 AN EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO MAIN. PLEASE SEE 250.24 AN
 EQUIPMENT GRND IS ONLY INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECT.
  
 2)NOTE: PLEASE VERIFY AIC RATINGS AT
 THIS TIME. 110.9/ 215.5
  
 3)NOTE: PLEASE SIZE SEC'S, SERVICE IS
 SHOWN AS 250A'S. 3/0'S IS RATED FOR 200A
 'S PER 310.16. PLEASE SEE 230.42B
  
 4)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING FO EM/EXT LTS.
 REDLINED ON ORIG.
  
 5)NOTE: PLEASE SEE OCP FOR AHU'S 7.5KW
 TO BE SIZED PER 424.3B MIN 125%. SHOWN
 AS 40A. PLEASE VERIFY WITH NAMEPLATE
 ON UNITS.
  
 6)NOTE: PLEASE SEE NOTE #10, MENTIONS
 OPTIONAL 2" CONDUIT. THIS CONDUIT AND
 FEED FROMFIRST METER IS NOT OPTIONAL
 AT THIS TIME. TENANT SPACE WILL REQUIRE
 TENANT SEPARATION AT THIS TIME IF NOT
 INSTALLED.
  
 7)NOTE: PLEASE PROVIDE AMPERAGE FOR
 METERCANS SHOWN.
 RISER SHOWS BOTH125A MAINS COMING FROM
 ONE METER CAN.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  