| 2004-02-20 00:00:00 | ************* UNSAT **************** |
| | |
| | PLEASE SEE REVISED PLANS ARE COMING IN |
| | WITH ALL NEW ELECTRICAL SERVICE ETC. |
| | THE FOLLOWING ARE NEW NOTES AND NOTES |
| | FROM ORIGINAL REVIEWS THAT WERE REDLINED |
| | ON ORIG PLANS. |
| | |
| | 1)NOTE: PLEASE SEE NOTE #5, MENTIONS |
| | AN EQUIPMENT GROUNDING CONDUCTOR FROM |
| | METER TO MAIN. PLEASE SEE 250.24 AN |
| | EQUIPMENT GRND IS ONLY INSTALLED AFTER |
| | THE FIRST MEANS OF DISCONNECT. |
| | |
| | 2)NOTE: PLEASE VERIFY AIC RATINGS AT |
| | THIS TIME. 110.9/ 215.5 |
| | |
| | 3)NOTE: PLEASE SIZE SEC'S, SERVICE IS |
| | SHOWN AS 250A'S. 3/0'S IS RATED FOR 200A |
| | 'S PER 310.16. PLEASE SEE 230.42B |
| | |
| | 4)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING FO EM/EXT LTS. |
| | REDLINED ON ORIG. |
| | |
| | 5)NOTE: PLEASE SEE OCP FOR AHU'S 7.5KW |
| | TO BE SIZED PER 424.3B MIN 125%. SHOWN |
| | AS 40A. PLEASE VERIFY WITH NAMEPLATE |
| | ON UNITS. |
| | |
| | 6)NOTE: PLEASE SEE NOTE #10, MENTIONS |
| | OPTIONAL 2" CONDUIT. THIS CONDUIT AND |
| | FEED FROMFIRST METER IS NOT OPTIONAL |
| | AT THIS TIME. TENANT SPACE WILL REQUIRE |
| | TENANT SEPARATION AT THIS TIME IF NOT |
| | INSTALLED. |
| | |
| | 7)NOTE: PLEASE PROVIDE AMPERAGE FOR |
| | METERCANS SHOWN. |
| | RISER SHOWS BOTH125A MAINS COMING FROM |
| | ONE METER CAN. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |