| Plan Review Notes For Permit 03080986 |
| Permit Number |
03080986 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-10-28 00:00:00 | PLANS REDLINED **** | | | | | | 1)NOTE: PLEASE SEE THAT NO MEANS OF | | | EGRESS LIGHTING IS SHOWN AS EXISTING OR | | | NEW LEAVING SIDE DOOR. LS 101 5-8 | | | THIS WAS NOTE ON FIRST TWO REVIEWS. | | | | | | 2)NOTE: PLEASE SEE EXT/EM LTS ARE BEING | | | SHOWN ON PANEL SCHEDULE AND CAN NOT | | | LOCATE EM LTS ON PLANS? ALSO MUST BE | | | CIRCUITED PER 700.12E AS NOTED ON FIRST | | | TWO REVIEWS. | | | | | | | | | | | | THESE ARE NOTES REDLINED. |
|