Plan Review Notes
Plan Review Notes For Permit 03080986
Permit Number 03080986
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-07 00:00:00************** UNSAT *******************
  
  
 1)NOTE: PLEASE SEE THAT IT APPEARS THE
 SAME PLAN CAME BACK IN W/OUT ANY CHANGES
 ?? MAYBE NOTES DID NOT GO TO ARCH FROM F
 ROM FIRST REVIEW.?
  
 2)NOTE: PLEASE SEE 424.3 FOR MIN SIZE
 OF OCP TO BE 125% FOR HEAT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]