| 2003-10-09 00:00:00 | PASSED: ALTERNATE PRODUCT APPROVALS |
| | SUBMITTED 10/8/03. |
| | |
| | NOTE: THE UNSUITABLE SYSTEMS HAVE BEEN |
| | STRUCK FROM THE SUBMITTED JOHNS MANVILLE |
| | CORP. BUILT-UP ROOFING PRODUCT APPROVAL |
| | NOA# 01-0524.13 |
| 2003-10-02 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 9/19/03: |
| | |
| | 3) THE SUBMITTED JOHNS MANVILLE CORP. |
| | BUILT-UP ROOFING PRODUCT APPROVAL |
| | NOA# 01-0524.13 HAS NOT BEEN MARKED TO |
| | IDENTIFY WHCH SYSTEM IS TO BE USED.OF |
| | THE AVAILABLE SYSTEMS, SOME HAVE A MAX. |
| | DESIGN PRESSURE RATING OF -45 PSF AND |
| | REFERENCE GENERAL LIMITATION #9 WHICH |
| | DOES NOT ALLOW RATIONAL ANALYSIS OR |
| | EXTRAPOLATION FOR ENHANCED FASTENING AT |
| | THE EDGE OR CORNER ZONES.PLAN SHEET #1 |
| | STATES THAT THE DESIGN PRESSURE AT THE |
| | EDGE STRIP IS -59.2 PSF AND THAT AT THE |
| | CORNER ZONES IS -89.0 PSF, BOTH OF WHICH |
| | EXCEED THE ABOVE-MENTIONED DESIGN |
| | PRESSURE RATING.MARK THE PRODUCT |
| | APPROVAL TO SPECIFY A SYSTEM WHICH, WITH |
| | ENHANCED FASTENING IF APPROPRIATE, HAS |
| | A DESIGN PRESSURE RATING WHICH EXCEEDS |
| | THE DESIGN PRESSURES.ALTERNATIVELY, A |
| | SEPARATE ROOFING PERMIT APPLICATION WILL |
| | BE REQUIRED. |
| | |
| | 4) HURRICANE MISSILE IMPACT PROTECTION. |
| | CONTRARY TO ROBERT BELL'S COMMENT |
| | RESPONSE LETTER, THE SUBMITTED PRODUCT |
| | APPROVALS FOR THE STOREFRONT SYSTEM AND |
| | THE NARROW STILE DOOR BOTH STATE THAT |
| | THESE PRODUCTS ARE NOT IMPACT RATED AND |
| | WILL REQUIRE THE PROVISION A HURRICANE |
| | MISSILE IMPACT PROTECTION SYSTEM. |
| | PROVIDE ALTERNATIVE PRODUCT APPROVALS |
| | OR SUBMIT A PRODUCT APPROVAL FOR STORM |
| | SHUTTERS. |
| | |
| | 6) STOREFRONT PRODUCT APPROVAL.SEE |
| | COMMENT #4 ABOVE. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |