2003-09-19 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIDY NEW OR EXISTING
 REQ'D SIGN CIRCUIT PER 600.5
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR POSSIBLE NOTES FOR EMERGENCY LTS?
  
 3)NOTE: PLEASE CIRCUIT EM/EXT LTS PER
 700.12E
  
 4)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING WHAT APPEARS TO BE SIDE EXIT?
 LS 101 5-8 EXISTING? OF SOME TYPE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  