| Plan Review Notes For Permit 03080886 |
| Permit Number |
03080886 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-28 00:00:00 | | | | THE FOLLOWING COMMENTS WHERE REDLINED ON | | | THE PERMIT SET OF PLANS, AND ARE STILL | | | IN VIOLATION OR AT LEAST NOT SHOWN AS | | | CORRECTED. ACTUAL LOCATIONS MUST BE | | | VERIFIED FOR "AS-BUILT" DRAWINGS. | | | | | | 1} A SMOKE DETECTOR IS REQUIRED OUTSIDE | | | AND IN THE IMMEDIATE VICINITY OF THE | | | MASTER SUITE. THE PLAN INDICATES 2 | | | INSIDE THAT SUITE. PLEASE VERIFY ACTUAL | | | LOCATION.COMPLY WITH 8-1.4.1.6.2 | | | NFPA-72. | | | | | | 2} BATH #2 NEEDS A RECEPTACLE ADDED OR | | | THE ONE SHOWN TO BE RELOCATED TO COMPLY | | | WITH 210.52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|