| Plan Review Notes For Permit 03080883 |
| Permit Number |
03080883 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-12-11 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-ENGINEER OF RECORD TO SIGN, SEAL AND | | | DATE ALL DRAWINGS THAT HAVE STRUCTURAL | | | NOTES & STRUCTURAL DETAILS. RESUBMIT | | | 2 COPIES WITH ENGINEER'S SEAL AND | | | HIS COMPLETE INFORMATION AS REQ'D BY | | | CHAPTER 471 FLORIDA STATUTES. | | | 2-REVISE SURVEY TO MATCH DIMENSIONS ON | | | REVISED PLANS. | | | 3-REVISE ENERGY CALCULATIONS. A/C AREA | | | TO MATCH REVISED PLANS. | | | 4-MAKE SURE EGRESS WINDOW ON BERDROOM | | | #3 HAS 24" MIN. CLEAR HEIGHT OPENING | | | AND WINDOW SILL IS NOT MORE THAN 44" | | | AS REQ'D BY SEC. 1005.4 FBC 2001. | | | 5-CLARIFY DESIGN CRITERIA ON SHEET S-2. | | | NEED TO INCLUDE 10PSF LIVE LOAD FOR | | | ATTIC WITHOUT STORAGE AS REQUIRED BY | | | TABLE 1604.1 FBC 2001. |
|