Plan Review Notes
Plan Review Notes For Permit 03080883
Permit Number 03080883
Review Stop B
Sequence Number 3
Notes
Date Text
2003-10-21 00:00:00THIRD CHECKLIST:
 1-SHEET S-2: A)UPDATE TRUSS ANCHOR
 SCHEDULE TO COMPLY WITH SEC. 1609.4.3
 FBC 2001. WHICH DOESN'T ALLOW STEEL
 STRESS TO BE INCREASED.
 B)AVERAGE ULTIMATE LOAD OF CONNECTORS
 SHOULD NOT BE USED FOR DESIGN. REVISE.
 C)REVISE ROOF LOADING AS REQUIRED. SEE
 TABLE 1606.1 FBC 2001. NEED TO INCLUDE
 ATTIC LIVE LOADS.
 D)REVISE FASTENERS FOR CONNECTOR SIMPSON
 CC44. IT'S TO BE USED WITH BOLTS, NOT
 WITH NAILS. SEE CATALOGUE.
 E)NEED TO KEY ALL CONNECTORS ON SECOND
 FLOOR FRAMING PLAN AND ROOF FRAMING
 PLAN. THERE ARE SOME CONNECTIONS THAT
 HAVE NO CONNECTORS SPECIFIED.
 F)UPLIFT VALUES GIVEN ON THE ANCHOR
 SCHEDULE ARE NOT CORRECT. SEE USP AND
 SIMSPN CATALOGUE AND REVISE AS REQ'D.
 SEE COMMENTS ON PLANS.
 G)SHOW ON SECOND FLOOR FRAMING PLAN THE
 BEAMS REFERENCED ON THE BEAM SCHEDULE
 ON SHEET S-1. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 2-SHEET S-3: A)REVISE TRUSS CONNECTORS
 AS REQUIRED. SEE COMMENTS.
  
 2-CLARIFY WHY WINDOW D WAS DELETED FROM
 WINDOW SCHEDULE, BUT STILL SHOWN ON
 THE EXTERIOR ELEVATIONS.
 3-SPECIFY DRAFSTOPPING MATERIAL AND LOCA
 TION ON 2ND FL. FRAMING PLAN. SEE SEC.
 2305.2.2 FBC 2001. **NOTE:FIREBLOCKING
 IS NOT THE SAME AS DRAFTSTOPPING.
 4-RESUBMIT PRODUCT APPROVAL FOR GARAGE
 DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED ON THIS PROJECT.
 5-SHEET S-1: CLARIFY CONNECTOR SIMPSON
 CC4 SPECIFY ON PLAN. SEE COMMENTS.
 IT DOESN'T WORK ON SUCH LOCATION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-CLARIFY/UPDATE/REVISE TRUSS ANCHOR
 SCHEDULE TO BE USED: SEE SHEET A-7 AND
 S-2 AND REVISE AS REQUIRED.
 7-REMAINDER: ARCHITECT TO INCLUDE HIS
 LICENSE NUMBER AND ALL INFORMATION AS
 REQ'D BY CHAPTER 481 FLORIDA STATUTES
 WHEN SUBMITTING INFORMATION FOR
 PUBLIC RECORDS.
 8-RE-SUBMITTAL FEES WILL BE CHARGED FOR
 MULTIPLE REVIEWS AT RE-SUBMITTAL TIME.
  
  
 IF ARCHITECT HAS ANY QUESTIONS REGARDING
 THE REVIEW COMMENTS, PLEASE CALL JULIO
 GOMEZ AT 805-6712.