2003-10-07 00:00:00SECOND CHECKLIST:
 1-MISSING SECOND FLOOR PLAN AS REQUESTED
 ON FIRST REVIEW. SECTION 104.3.1.1 OF
 CITY AMENDMENTS TO FBC 2001.
 2-SURVEY IS MISSING FROM PACKAGE.
 3-CLARIFY WHY WAS WINDOW D DELETED FROM
 WINDOW SCHEDULE, BUT STILL SHOWN ON
 EXTERIOR ELEVATIONS.
 4-PROVIDE COMPLETE SECTION/DETAIL WITH
 COMPLETE SPECS FOR BALCONIES & MASTER
 TERRACE. SECTION 104.2.1.2 OF THE CITY
 AMENDMENTS TO FBC 2001. INCLUDE GUARD-
 RAIL DESIGN. SEE SEC. 1015 FBC FOR
 BOTTOM RAIL.
 5-DESIGN PRESSURES FOR DOORS AND WINDOWS
 SHOWN ON PLANS DON'T REFLECT ANY OF
 THOSE SHOWN ON TABLES OF SEC. 1606 IF
 THE DESIGN CRITERIA IS FBC 2001.
 CLARIFY HOW ARE THESE DESIGN PRESSURES
 CALCULATED. EVEN THE DESIGN PRESSURES
 SHOWN ON THE SAME PLANE SHOW SOME
 DISCREPANCIES ACCORDING TO SIZE AND
 LOCATION. SEC. 104.2.1.2 AMENDMENTS TO
 FBC 2001.
 6-TWO STORY WALL SECTION: A)DOESN'T SHOW
 LOAD CONTINUITY FROM ROOF TO FOOTING.
 IT DOESN'T SHOW HOW WOOD FRAMED WALL
 IS ATTACHED TO FLOOR TRUSS & TO BOND
 BEAM.
 B)BOND BEAM IS NOT SPECIFIED.
 C)SPECIFY LOCATION OF STRONG-WALL
 SHEARWALLS. ALSO, DRAWINGS IS SHOWING
 ROD, NOT THIS TYPE OF CONNECTION.
 D)CLARIFY NAILING OF SP6.
 E)SEE PLANS FOR COMMENTS AND RETURN
 REDLINED DRAWINGS TO EXPEDITE REVIEW.
  
 7-ONE STORY WALL SECTION: REVISE USP
 CONNECTOR TO COMPLY WITH SEC. 1609.4.3
 FBC 2001. STEEL STREES INCREASE IS NOT
 ALLOWED. INFORMATION GIVEN ABOUT 133%
 AND 160% IS INCORRECT. THIS IS WHAT IS
 NOT ALLOWED.
 8-ARCHITECT TO SPECIFY THE FIREBLOCKING
 MATERIAL. ALSO, PROVIDE GENERAL SPECS
 FOR FIREBLOCKING AT ALL CONCEALED
 SPACES AS REQUIRED BY SEC. 2305 FBC.
 INCLUDING FIREBLOCKING AT STAIRS.
 9--UPDATE TRUSS ANCHOR SCHEDULE TO
 COMPLY WITH SECTION 1609.4.3 FBC. THE
 133% AND 160% INCREASE IS NOT ALLOWED.
 10-GARAGE STRUCTURAL BUCK DETAIL:CLARIFY
 WHY ANCHORS ARE NOT EQUALLY SPACEDIN
 ORDER TO EQUALLY DISTRIBUTE THE LOAD
 TO THE SUBSTRATE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-WINDOW BUCK DETAIL IS NOT CLEAR. SEE
 SEC. 1707.4.4.2 FBC 2001 AND SHOW HOW
 IS BUCK INSTALLED TO PROVIDE COMPLETE
 SUPPORT OF WINDOW. ALSO, DETAIL FOR
 DOOR BUCK SHOW A WINDOW, NOT A DOOR.
 REVISE AS REQUIRED.
 12-SHOW DRAFSTOPPING MATERIAL & LOCATION
 ON 2ND FLOOR FRAMING PLAN. SEC. 2305
 FBC 2001.
 13-PROVIDE BEAM SCHEDULE.
 14-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOOR WITH SIDELITES ASSEMBLY AS
 SHOWN ON PLANS. OTHERWISE PROVIDE SITE
 SPECIFIC ENGINEERING.
 B)FRENCH DOORS WITH SIDELITES (THERE ARE
 6 COPIES SUBMITTED BUT DRAWINGS ARE NO
 LEGIBLE. ONLY NEED TWO COMPLETE & WITH
 CLEAR DRAWINGS.
 C)STORM SHUTTERS NEED LEGIBLE DRAWINGS
 AND CHECK ON DRAWINGS INSTALLATION
 TYPE & ANCHOR AND SPACING TO BE USED.
 WHY USING STORM PANELS IF ALL OTHER
 DOORS AND WINDOWS ARE IMPACT GLAZING?
 D)PROVIDE DRAWINGS (2 LEGIBLE COPIES)
 FOR GARAGE DOORS PRODUCT APPROVAL.
 E)FLAT ROOF SYSTEM.
 15-ARDAMAN & ASSOCIATES ENGINEER LETTER
 REGARDING FOOTING SIZE NEED TO HAVE
 ORIGINAL SEAL, SIGNATURE, DATE AS
 REQUIRED BY CHAPTER 471 FL STATUTES.
 16-PROVIDE COMPLETE SECTION DETAIL AT
 GABLE END. SEE SEC. 2313.4 FBC 2001
 FOR SPECIFIC REQUIREMENTS.
 17-SPECIFY LIVE LOADS USED FOR DESIGN.
 SEE TABLE 1604.1 FBC 2001. THIS INFO.
 IS REQUIRED FOR PROPER DESIGN OF THE
 ENGINEERED TRUSSES. INCLUDE ATTIC
 LIVE LOADS.
  
 NOTE: CALLED ARCHITECT TO GO OVER THE
 DEFICIENCIES OF THE DRAWINGS BUT
 HE WAS OUT ON VACATION.