| Plan Review Notes For Permit 03080883 |
| Permit Number |
03080883 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1) SHT A-7 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. | | | A) WASH MACHINE NOT VENTED, REQUIRES A | | | STANDPIPE, & REQUIRES A CLEANOUT LOCATED | | | 4' ABOVE THE FLOOR. SECTIONS 708.10, | | | 802.4, & 901.2.1. | | | B) BATH #3 2ND FLOOR SHOWS A TUB ON THE | | | FLOOR PLAN BUT HAS A SHOWER ON THE RISER | | | DIAGRAM. LAV SHOWN AS CONNECTING BELOW | | | THE FLOOR ON THE RISER AND TUB (SHR) NOT | | | VENTED. SECTION 104.2.1 | | | C) BATH #2 SHOWN AS CONNECTING TO BLDG. | | | DRAIN UNDER THE SLAB ON RISER, BUT ITS | | | ON THE SECOND FLOOR ON FLOOR PLAN. | | | SECTION 104.2.1 | | | 3) LICENSE NUMBER REQUIRED ON EACH SHEET | | | PER 61G1-16.004 (TITLE BLOCK) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|