Plan Review Notes
Plan Review Notes For Permit 03080883
Permit Number 03080883
Review Stop B
Sequence Number 1
Notes
Date Text
2003-09-12 00:00:00BUILDING CHECKLIST:
 1-SURVEY: A)FLOOD ZONE A5. SHOW PROPOSED
 FINISH FLOOR ELEVATION.
 B)REVISE PROPERTY ADDRESS. THIS IS WEST
 PALM BEACH. NOT RIVIERA BEACH.
 C)PROPOSED BUILDING IS 2 STORY, NOT ONE.
  
 2-SEE ENGINEER RECOMMENDATIONS
 ON PAGE 3 OF SOIL TEST REPORT: 10 MIL
 MINIMUM VAPOR BARRIER, ISOLATION OF
 GROUND FLOOR SLAB FROM COLUMN AND WALL
 FOUNDATIONS OR SPECIAL RECOMENDATIONS
 FOR MONOLITHIC FOOTING AND CHECK MIN.
 FOOTING SIZE FOR WIDTH AND EMBEDMENT
 INTO GRADE. SEC. 1804.2.2 AND SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-MISSING STRUCTURAL SHEETS S-2 AND S-3.
 4-ARCHITECT TO DESIGN CONTROL JOINTS IN
 CONCRETE SLAB OR SPECIFY SUPPORT AND
 SPACING FOR WWM. SEC. 1909.3 FBC 2001.
 5-ENERGY CALCULATIONS: A)SECOND FLOOR IS
 WOOD FRAMING. REVISE WALL TYPE INSUL.
 ANDAREA AS REQUIRED. ADJUST CONCRETE
 WALL ACCORDINGLY.
 B)REVISE OWNER INFORMATION AND COMPLETE
 ALL INFORMATION ON TOP OF FORM.
 6-COVER PAGE NEEDS TO BE SEALED, SIGNED
 AND DATED AS WELL AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES.
 7-SHEET A-1: A)REVISE DESIGN PARAMENTERS
 AND ASSUMPTIONS NOTES: THERE IS NOT
 SBCC, BUT FBC 2001.
 B)WHERE IS THE VELOCITY PRESSURE TAKEN
 FROM?. SEE CHAPTER 16 FBC 2001.
 C)WHY SHEARWALLS ARE NOT REQUIRED?
 **NOTE: SEE SEC. 1606.1.7 FBC 2001 FOR
 INFORMATION REQUIRED ON DRAWINGS.
 8-SHEET A-2: A)CLARIFY IF USING STORM
 SHUTTERS OR MISSILE IMPACT GLAZING.
 IF USING NON-IMPACT GLAZING, THEN
 SPECIFY AREAS TO HAVE SAFETY GLAZING.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 B)NEED A COMPLETE BATHROOM ON 1ST FLOOR
 WITH DOOR THAT ALLOWS 29" MIN. CLEAR
 OPENING. SEC. 11 OF CHAPTER 11 FBC/01.
 **ALSO, FLOOR PLANS MISSING SPECS ON
 SIZES OF INTERIOR DOORS.
 C)OFFICE ON FIRST FLOOR FLOOR IS ALSO A
 BEDROOM. NEED EGRESS WINDOWS THAT
 COMPLY WITH SEC. 1005.4. FBC 2001.
 D)PROVIDE COMPLETE DETAILS/SPECS FOR
 HANDRAILS AND GUARDARAILS. NOTE AS PER
 CODE IS NOT ACCEPTABLE. NEED TO BE
 SPECIFIC. SEE SECTIONS 1007, 1015 AND
 1608.2 FBC 2001 FOR DESIGN OPENING
 CLEARANCES AND STREHGTH.
 E)REVISE ATTIC ACCESS LOCATION. THERE IS
 A SECOND FLOOR ABOVE. SEE PLANS.
 F)WINDOW SCHEDULE: WINDOW F NEED PRODUCT
 APPROVAL OR COMPLETE SITE SPECIFIC
 ENGINEERING.
 G)REVISE GENERAL NOTE #10. ALL EQUIPMENT
 TO BE 6" MIN.ABOVE BASE FLOOD ELEVATIO
  
 9-SHEET A-3: A)SPECIFY SAFETY GLASS
 WHERE REQUIRED. SEC. 2405.2 FBC 2001.
 SEE PLANS.
 B)PROVIDE COMPLETE DETAIL/SECTIONS AT
 MASTER LOGGIA AND BALCONIES. SEC.
 104.2.1.2 CITY AMENDMENTS AND SECTIONS
 1015 AND 1608.2 FBC 2001.
 C)REVISE NOTE #10. SEE COMMENTS ABOVE.
  
 10-SHEET A-4: A)WINDOWS DON'T MATCH SIZE
 SPECIFIED ON WINDOW SCHEDULE.
 B)PROVIDE ENGINEERING FOR CALCULATION
 OF DOORS AND WINDOWS DESIGN PRESSURES.
 THEY DON'T MATCH TABLE 1606.2B
 ACCORDING TO SIZE AND LOCATION. ALSO,
 SEE FOOTNOTE #1.
 C)THERE ARE SOME DESIGN PRESSURES THAT
 ARE NOT SPECIFIED. EG: DOORS.
 D)PROVIDE COMPLETE WALL/SECTION DETAIL
 THRU ENTRY DOOR WALL INCLUDING
 PARAPET. SEC. 104.2.1.2 CITY AMENDMENT
 E)PROVIDE COMPLETE SECTION/DETAIL FOR
 CONSTRUCTION OF CANTILEVERED BAYS FOR
 BAYWINDOWS. SEC. 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
  
 11-SHEET A-6: A)STUCCO ON FRAMED WALLS
 TO BE 7/8" MIN. ASTM C-926.
 B)REVISE SPECIFICATIONS GIVEN ON 2 STORY
 WALL SECTION AT FIRST FIRST FLOOR.
 THIS IS CONC. BLOCK, NOT WOOD FRAMING.
 C)SPECIFY CONNECTIONS AT TOP AND BOTTOM
 OF SECOND FLOOR STUDS.
 D)SIMPSON ST22 CONNECTOR DON'T PROVIDE
 RESISTANCE FOR LATERAL LOADS & WHAT'S
 THE UPLIFT LOAD CALCULATED TO RESIST.
 E)GABLE ENDS ARE NOT THE ONLY ROOF ZONE
 3. SEE FIGURE 1606.2(C) FBC 2001 AND
 REVISE ROOF SHEATHING NOTE.
 F)SPECIFY FIREBLOCKING ON BOTH WALL
 SECTIONS. AND ON STAIRS. SEE SECTION
 2305 FBC 2001. ALSO, PROVIDE GENERAL
 SPECIFICATIONS FOR FIREBLOCKING AT ALL
 CONCEALED SPACES.
 G)REVISE FOOTING SIZES AND VAPOR BARRIER
 THICKNESS. SEE SOIL TEST REPORT.
 H)REVISE INFORMATION GIVEN ON HORIZONTAL
 LOAD ZONES TABLE. SEE COMMENTS ON DWG
 AND TABLE 1606.2A FBC 2001.
 I)PROVIDE COMPLETE INFORMATION ON STAIR
 AND HANDRAIL DETAILS. SEE SECTIONS
 1007, 1015 AND 1608.2 FBC 2001.
 J)CLARIFY THICKNESS OF ROOF SHEATHING.
 5/8" OR 3/4". SEE SHEET A-8.
 K)FINISH ELEVATION TO BE 4" MIN. ABOVE
 FINISH GRADE. SECTIONS SHOW NONE.
 SEC. 1804.1.7 CITY AMENDMENTS TO FBC.
  
 12-SHEET A-7: A)UPDATE ANCHOR SCHEDULE
 AND ALL DETAILS THAT ARE AFFECTED BY
 SECTION 1609.4.3 FBC 2001 WHICH DOES
 NOT ALLOW THE STEEL STRESS TO BE
 INCREASED. IF USING SIMPSON CONNECTORS
 THEN, ONLY THE HIGH WIND-RESISTANT
 CONSTRUCTION CATALOGUE 2003 HAVE BEEN
 REVISED.
 B)GARAGE STRUCTURAL BUCK DETAIL: CLARIFY
 SPACING AND NUMBER OF ANCHORS. DETAIL
 SHOWS 9'-0" HIGH DOOR.
 **PLAN DETAIL SHOWS POURED CONCRETE COL.
 PLANS SHOW FILLED CELLS. CLARIFY.
 C)REVISE NOTE REFERING TO SBCCI. WE HAVE
 ADOPTED FBC 2001, NOT SBCCI.
 D)REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001.
 E)PROVIDE STRUCTURAL BUCK DETAIL FOR
 EXTERIOR DOORS TOO. NOTE: SEE PRODUCT
 APPROVAL IF 2X OR 1X BUCK IS REQUIRED.
 **ALSO, SEE SEC. 1707.4.4.2 FOR PROPER
 BUCK ATTACHMENT.
 F)REVISE INSULATION VALUE GIVEN ON WALL
 SECTION. SEE ENERGY CALCULATIONS.
  
 13-SHEET A-8: REVISE/CLARIFY NOTES. SEE
 COMMENTS ON PLAN.
 14-SHEET S-1: A)MISSING FOOTINGS FOR
 INTERIOR BEARING WALLS.
 B)PROVIDE COMPLETE SECTION/DETAIL FOR
 CONSTRUCTION OF CANTILEVERED BAYS.
 C)CLARIFY FOOTING BETWEEN GARAGE AND
 LAUNDRY. SEE COMMENTS ON PLAN.
  
 15-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 16-NEED RECORDED NOTICE OF COMMENCEMENT.
 17-PROVIDE SECOND FLOOR FRAMING PLAN.
 IT'S NOT LISTED IN THE COVER PAGE.
 **SHOW DRAFSTOPPING MATERIAL & LOCATION.
 SEE SEC. 2305.2.2 FBC 2001.
 18-ROOF FRAMING PLAN TO INDICATE ROOF
 NAILING ZONES, NAILING TYPE & SPACING.
 SEE SEC. 2306 CITY AMENDMENTS TO FBC.
 19-PROVIDE COMPLETE DETAIL/SPECS FOR
 CEILING INSTALLATION AT LOGGIAS. SEE
 ASTM C-926 AND ASTM C-1063 FOR
 STUCCO AND FASTENER SPECS. SECTION
 2504.2 FBC 2001.
 20-PROVIDE COMPLETE FRAMING DETAIL/SPECS
 FOR FRAMING AT ARCHED OPENINGS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 21-PROVIDE BEAM SCHEDULE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 22-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS WITH SIDELITES AND TRANSOM
 ABOVE SINGLE UNIT AS SHOWN ON PLANS.
 B)ARCHED WINDOWS.
 C)OVAL WINDOWS.
 D)GARAGE EXTERIOR SWING DOOR. SEE PLANS.
 E)FRENCH DOORS WITH SIDELITES SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 F)GARAGE DOOR THAT MATCHES ONE SHOWN ON
 PLANS.
  
 23-IF USING STORM SHUTTERS, THEN PROVIDE
 COMPLETE INFORMATION,LEGIBLE PRODUCT
 APPROVAL AND DRAWINGS, KEY PLAN AND
 INSTALLATION SCHEDULE AND MARK ON
 DRAWINGS THE SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE & SPACING
 TO BE USED.
 24-BUILDING VALUATION WAS UPDATED TO BE
 $327,579. ADDITIONAL FEES WILL BE
 ADDED TO REFLECT THIS REVISE VALUE.
  
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 CAD DRAWINGS TO EXPEDITE THE REVIEW
 PROCESS.