| Plan Review Notes For Permit 03080840 |
| Permit Number |
03080840 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-08-18 00:00:00 | PROVISO: | | | 1.A MINIMUM OF 4" AROUND THE AIR | | | HANDLER IS REQURIED PER 2001 FBC(M) | | | 603.1.3. | | | | | | 2.FLEX DUCT SHALL BE SUPPORTED AT | | | INTERVALS NOT GREATER THAN 5 FT. | | | | | | 3.OVERFLOW PROTECTION REQUIRED PER | | | 2001 FBC(M) 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|