Plan Review Notes
Plan Review Notes For Permit 03080840
Permit Number 03080840
Review Stop M
Sequence Number 2
Notes
Date Text
2003-08-18 00:00:00PROVISO:
 1.A MINIMUM OF 4" AROUND THE AIR
 HANDLER IS REQURIED PER 2001 FBC(M)
 603.1.3.
  
 2.FLEX DUCT SHALL BE SUPPORTED AT
 INTERVALS NOT GREATER THAN 5 FT.
  
 3.OVERFLOW PROTECTION REQUIRED PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.