| Plan Review Notes For Permit 03080809 |
| Permit Number |
03080809 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | PLAN REVIEW NOT A PERMIT APPLICATION. | | | | | | THE WIND LOAD CALCULATIONS, AND DESIGN | | | PRESSURE ARE REQUIRED TO COMPLY WITH | | | ASCE 7-98 FOR A 140 MPH ZONE. | | | | | | INCLUDE THE ANTENNA DISH/DEVICE AND ITS | | | CONNECTION TO THE 2" PIPE. | | | | | | PROVIDE AN ENGINEERING INVESTIGATION AS | | | ABOVE FOR THE PROPOSED EQUIPMENT CABINET | | | AND ITS ATTACHMENT TO THE BUILDING. | | | | | | SHOW THE ROUTE OF ANY CABLING, CONDUIT | | | OOR SIMILAR THAT WILL PENETRATE THE | | | ROOF AND/OR FLOORS OF THE BUILDING. |
|