| Plan Review Notes For Permit 03080784 |
| Permit Number |
03080784 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-24 00:00:00 | *****CORRECTIONS****** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEPARATE PERMITS REQUIRED. | | | | | | 2.)ADDITIONAL FEES DUE, $20.18 (VALUE | | | ADJUSTMENT, RADON).BZ231205 | | | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 4.)IMPROVEMENTS OVER 25% MUST COMPLY | | | WITH FBC3401.7.2, 2003 AMENDMENT. | | | | | | 5.)ENERGY CALCS REQUIRED, FBC13-101.2. | | | SIGN THE OWNER/AGENT LINE OF THE ENERGY | | | CALC. | | | | | | 6.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 7.)STUCCO OVER WIRE LATH IN A VERTICAL | | | APPLICATION TO BE 3COAT (7/8"), | | | FBC2504.2.2, ASTM1063. | | | | | | 8.)SMOKE DETECTORS REQUIRED TO COMPLY | | | WITH FBC905.2.2. | | | | | | 9.)SUBMIT PRODUCT APPROVALS FOR THE | | | WINDOW (2 COPIES). |
|