| Plan Review Notes For Permit 03080731 |
| Permit Number |
03080731 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-25 00:00:00 | THE STRUCTURAL CALCULATIONS SIGNED AND | | | SEALED BY THOMAS TWOMEY, PE DATED | | | 8/13/03 ARE NOT ACCEPTABLE. | | | | | | THE CALCULATIONS USE THE | | | NOMINAL SIZE OF THE LUMBER 3X12 RATHER | | | THAN THE ACTUAL 2 3/4"X11".THERE IS NO | | | FACTOR FOR DURATION OR AN INVESTIGATION | | | FOR DEFLECTION.IS THE PLASTER AND WOOD | | | LATH CEILING INCLUDED IN THE MISC. 5 | | | PSF?OTHER COLLATERAL LOADS SUSPENDED | | | BELOW, IE MECHANICAL AND SPRINKLER | | | SYSTEMS? |
|