2003-08-26 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY NEW OR EXISTING
 EM/EXT LTSAND CIRCUITING PER 700.12E
  
 2)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SHOW WINDOW RECEPTS. 210.62
  
 3)NOTE: PLEASE CLARIFY LOADS FOR TRACK
 LIGHTING 220.12B
  
 4)NOTE: PLEASE CLARFIY EQUIPMENT GROUND-
 ING TO AND FROM TRANSFORMER AND GROUND
 FOR TRANSFORMER 250.110, 250.30
 THIS CAN BE REDLINED IF NOT KNOWN AT
 THIS TIME DUE TO EXSITING INSTALLATION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717