| Plan Review Notes For Permit 03080724 |
| Permit Number |
03080724 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-26 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | EM/EXT LTSAND CIRCUITING PER 700.12E | | | | | | 2)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SHOW WINDOW RECEPTS. 210.62 | | | | | | 3)NOTE: PLEASE CLARIFY LOADS FOR TRACK | | | LIGHTING 220.12B | | | | | | 4)NOTE: PLEASE CLARFIY EQUIPMENT GROUND- | | | ING TO AND FROM TRANSFORMER AND GROUND | | | FOR TRANSFORMER 250.110, 250.30 | | | THIS CAN BE REDLINED IF NOT KNOWN AT | | | THIS TIME DUE TO EXSITING INSTALLATION. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|